9 Modbus RTU – integrated Modbus port specification
9.3 Modbus register map
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
55
Power objects are presented as fixed-point values in either the two-register
fixed-point data format or the four-register coding format.
The two-register format is displayed in kilowatt hours.
404981
406517
1374
1974
Counter - external actuation
1)
–
1
404983
406519
1376
1976
Time of last actuation
(year, month, day, hour, minute, second)
–
405009
406545
1390
1990
Operating time
2)
in minutes
min
1
405011
406547
1392
1992
Operating time
2)
in hours
h
1
405013
406549
1394
1994
Operating time
2)
in days
d
1
405015
406551
1396
1996
Residual life
3)
points
–
1) An external actuation is a switching operation that is not initiated by the trip unit, such as manual switching, switching via an externally wired remote
operator or the actuation of a push-to-trip button.
2) The operating time counter will start as soon as the device is energized, either autonomously or through an external power supply.
3) 0 points
≙
100 % residual life
10.000 points
≙
0 % residual life
Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100)
Register number
Register address
(HEX)
Object
IEEE floating
point
Fixed point
(FP)
IEEE floating
point
Fixed point
(FP)
Description
(Values in brackets reflect the
American notation.)
Unit
Scale
factor (FP)