10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
112
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
–
20D7
Active energy (reverse)
Wh
1
–
20D8
Active energy combined (= f reverse)
Wh
1
–
20D9
Apparent energy
VAh
1
2054
20DA
Peak reactive power demand
Var
1
2055
20DB
Peak apparent power demand
VA
1
205A
20E0
Active power demand
W
1
205B
20E1
Reactive power demand
Var
1
205C
20E2
Apparent power demand
VA
1
205D
20E3
Minimum value - I
L1
(IA)
A
10
205E
20E4
Maximum value - I
L1
(IA)
A
10
205F
20E5
Minimum value - I
L2
(IB)
A
10
2060
20E6
Maximum value - I
L2
(IB)
A
10
2061
20E7
Minimum value - I
L3
(IC)
A
10
2062
20E8
Maximum value - I
L3
(IC)
A
10
2063
20E9
Minimum value - I
G
(IG)
A
10
2064
20EA
Maximum value - I
G
(IG)
A
10
2065
20EB
Minimum value - I
N
(IN)
A
10
2066
20EC
Maximum value - I
N
(IN)
A
10
2067
20ED
Minimum value - U
L1
(VA)
V
10
2068
20EE
Maximum value - U
L1
(VA)
V
10
2069
20EF
Minimum value - U
L2
(VB)
V
10
206A
20F0
Maximum value - U
L2
(VB)
V
10
206B
20F1
Minimum value - U
L3
(VC)
V
10
206C
20F2
Maximum value - U
L3
(VC)
V
10
206D
20F3
Minimum value - U
L1-N
(VAN)
V
10
206E
20F4
Maximum value - U
L1-N
(VAN)
V
10
206F
20F5
Minimum value - U
L2-N
(VAN)
V
10
2070
20F6
Maximum value - U
L2-N
(VAN)
V
10
2071
20F7
Minimum value - U
L3-N
(VAN)
V
10
2072
20F8
Maximum value - U
L3-N
(VAN)
V
10
2073
20F9
Overload pre-warning
%
1
2081
2107
Counter - I
sd
, I
i
tripping
–
1
2082
2108
Counter - I
r
, I
g
tripping
–
1
2083
2109
Operations counter
–
1
2084
210A
Counter - I
sd
tripping
–
1
2085
210B
Counter - I
i
tripping
–
1
2086
210C
Counter - bypass tripping
–
1
Index (Hex)
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit
Scale
factor (FP)