![background image](http://html1.mh-extra.com/html/eaton/power-xpert-pxr-10/power-xpert-pxr-10_manual_4153055133.webp)
10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
129
Table 73: Remote control - EtherCAT
10.2.3.6 Date and time
The release supports the reading and writing of real-time clock information
by the external communication module EtherCAT.
Eight registers, starting with index number 215E, are reserved for this
purpose.
Table 74: Real-time clock - EtherCAT
10.2.3.7 Primary status codes
Table 75: Primary status codes - EtherCAT
Command
group
Definition
Bit
Byte 2
Byte 1
Byte 0
–
Reset
Reset the trip
0
0
2
Reset the min./max. values of the L-N voltages1)
0
1
15
Reset the min./max. values of the L-L voltages1)
0
1
14
Reset the peak power requirement1)
0
0
4
Reset all min./max. values
0
1
4
Reset the energy1)
0
0
8
Reset the power-up display
0
0
3
Maintenance
mode
Activate the maintenance mode
1
0
8
Deactivate the maintenance mode
1
0
9
Index [Hex]
Definition
Data range
215E
Month
1 - 12
215F
Day
1 - 31
2160
Year
2000 - 2099
2161
Day of the week
1 = Sunday
…
7 = Saturday
2162
Hour
0 - 23
2163
Minute
0 - 59
2164
Seconds
0 - 59
2165
1/100 of a second
0 - 99
Code
Meaning
0x01
open
0x02
closed
0x03
tripped
0x04
Alarm active
0x0D
Threshold value active