10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
151
10.3.4.4 Event logs
A trip event provides historical values for the data objects at the time the
event has occurred. The trip unit classifies the event information in order to
be able to provide a different quantity for each type. The Profinet
communication can only access the historical summary, as well as the trip
and event data.
Table 88: Event classification - Profinet
A single trip may be registered under multiple event types. For example, a
protective trip may be recorded in the summary log (
table 90).
Event logs information is accessed via API: 0 and indexes according to
→
tables 89, 90 and 91.
If the event type selection is written to index 13C, the first and last event ID
can be retrieved from indexes 13D and 13E, respectively, in order to
determine the range of events that have been stored for the selected event
type. Index 13F is a R/W register for selecting the ID of the event in question.
If the requested event has been recorded by the device, indexes 140 and
141 will supply both the ID of the previous event and that of the next event.
If the device has not recorded the event in question, the exception code can
be queried by requesting the Modbus communication status of the ECAM
from the controller via a dedicated industrial protocol object (via API: 0 and
index 167).
The date and time at which the requested event occurred are read in log 2142,
with the same date and time description as in
This value corresponds to the time at which the historical event occurred.
Log 143 indicates the data content of the selected event type. This is a
constant value for the three event types supported by the module.
The event data also provide a valid bit for each data object, starting with
index 144. If bit 0 is set to 1, the initial data will be valid for the current trip
type, bit 1 for the second data object, bit 2 for the third data object, and so
forth.
The number of valid bit registers is calculated as.
(number of data objects - 1)/16
Event type
Quantity of
numbers
stored
Description of the event log
Summary
200
Tripping
10
Alarms
10
→
For more information on the exception codes, see