10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
117
Table 66: Setting group 0: “System group” - EtherCAT
Index
(Hex)
Bit
field
Mask
field
Setpoint name
R/W
Format
Description or value
Unit
2002
15 - 0
Password
W
–
0000 (default setting
–
2003
15 - 0
0xFFFFFF
Group 0 = system
R/W
0x00FF
–
2004
12 - 0
0x1FFFF
Rated current
R
Encoded
NZM2: 25, 40, 63, 90, 100, 140, 160, 200, 220,
250, 300
NZM3: 250, 350, 400, 450, 600, 630
NZM4: 550, 600, 630, 800, 875, 1000, 1200, 1250,
1400, 1600
A
2005
2 - 0
0x0007
Frame size
R
Encoded
The frame size indicates the breaker type.
11: NZM2
12: NZM3
13: NZM4
–
2006
3 - 0
0x000F
Trip type version -
part 1
R
Encoded
Bit 0: LdSel: with overload protection I
r
= 1
Bit 1: SdSel: with short-time delayed short-circuit
protection I
sd
= 1
Bit 2: InstSel: with instantaneous short-circuit
release I
i
= 1
Bit 3: GfSel: with ground-fault protection I
g
= 1
Bit 4: ARMSel: with maintenance mode = 1
Bit 5: OvrideSel: with instantaneous release func-
tion = 1
Bit 6: not used
Bit 7: MotorSel: with motor-protection function =
1
Bit 8: NeuSenorSel:
0: 3-pole device
1: 4-pole device
Bit 9: ThermalSel: with thermal memory = 1
Bit 12: VoltSel: with voltage meter = 1
Bit 13:
0: PXR20
1: PXR25
–
2007
Trip type version -
part 2
R
Encoded
Bit 0: ModbusSel: with integrated Modbus RTU
= 1
Bit 1: CAMSel: with CAM RS422 = 1
Bit 2: IOModuleSel: with IO module = 1
Bit 3: RelaySel: with relay module = 1
Bit 4: ZSISel: with zone selectivity = 1
Bit 12: NZM_ACB_Sel: degree of protection
0: IZMX
1: NZM
Bit 13: IECSel:
0: UL
1: Standard IEC
–
2008
8
0x0100
Maintenance
mode: state
R
Encoded
0: off
1: on
–
BBE
0x0001
Maintenance
mode:
remote control
R/W
Encoded
0: off
1: on
–
2009
2 - 0
0x0007
Maintenance
mode: Trip setting
R/W
Encoded
1: 2.5 x I
n
2: 4 x I
n
3: 6 x I
n
4: 8 x I
n
5: 10 x I
n
A