10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
83
10.1.2 IP configuration/DIP Switch Settings
The DIP switches are used to configure the device’s fieldbus addresses.
Flipping a single switch adds the switch specific value to the total address
value. As a result, values in a range from 0 to 255 can be configured that
way.
Table 45: Fieldbus address configuration via DIP switch
For example, flipping switches 4 and 6 results in the address 40.
Figure 20: DIP switches flipping example
The valid settings for EtherNet/IP are shown on
Table 46: Fieldbus address configuration via DIP switch
Switch
1
2
3
4
5
6
7
8
Value
1
2
4
8
16
32
64
128
Switches
Setting Value
Remarks
000
If the DIP switches are set to 0, the IP address settings stored in the NV-memory of the
device are used.
The factory default behaviour is DHCP.
The IP address settings can be configured by the IPconfig tool.
The tool can be downloaded here:
https://www.eaton.com/digitalnzm
001
If the DIP switches are set to 1, the address settings of the device are as follows:
IP address: 192.168.1.1
Subnet mask: 255.255.255.0
Default Gateway: 192.168.1.2
001 - 254
If the DIP switches are set in the range from 1 to 254, the IP address settings of the device
are determined by the switches:
IP address: 192.168.1.<DIP Switch Setting>
Subnet mask: 255.255.255.0
Default Gateway: 192.168.1.1
255
Invalid Setting. Device will not start-up properly.