Chapter 4
UPS System Installation
4.1
Preliminary Installation Information
W
A
R
N
I
N
G
Installation should be performed only by qualified personnel.
A
V
E
R
T
I
S
S
E
M
E
N
T
!
L’installation ne doit être effectuée que par du personnel qualifié.
Refer to the following while installing the UPS system:
S
Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and
installation notes.
S
Do not tilt the cabinets more than
"
10° during installation.
S
Remove the conduit landing plates to add conduit landing holes as required. Plate
material is 16 gauge steel (1.5 mm/0.06
”
thick).
S
If perforated floor tiles are required for ventilation, place them in front of the UPS.
4.2
Unloading the ISBM with UPM Section from the Pallet
The ISBM cabinets with a UPM or UPMs are joined and bolted to a wooden pallet
supported by wood skids. They are referred to as the UPS.
W
A
R
N
I
N
G
The ISBM with UPM or UPMs section is heavy (see Table 3‐1). If unpacking and unloading instructions are
not closely followed, the cabinets may tip and cause serious injury.
A
V
E
R
T
I
S
S
E
M
E
N
T
!
Les sections de l’onduleur sont lourdes (voir le tableau 3-1). Suivre attentivement les instructions de
déchargement et de déballage pour éviter de renverser les armoires, ce qui pourrait causer de graves
blessures.
C
A
U
T
I
O
N
S
Do not tilt cabinets more than 10° from vertical.
S
Lift the cabinets only with a forklift or damage may occur.
Figure