INTRODUCTION
Eaton
Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
S
P-164000563 Rev 1
www.eaton.com/powerquality
1-4
1.4
Options and Accessories
Contact an Eaton sales representative for information about the following options.
1.4.1
Integrated Battery Cabinets
Battery backup protection can be provided by equipping the UPS system with Eaton
9395P battery cabinets containing sealed lead‐acid, maintenance‐free batteries. The
cabinets are designed for standalone installation and may be installed adjacent to the
UPS or in a separate location. The recommended installation location for adjacent
battery cabinets is on the right side of the UPS cabinet to allow for future expansion
using an external module.
1.4.2
Field Installed UPM
A Field Installed UPM (FI-UPM) provides redundancy for the Eaton 9395P. The
FI-UPM may be installed at any time in the future. The module cabinet is installed on
the left side of the ISBM section and is wired directly to the UPS. No input or output
wiring changes are needed for adding redundancy. Operation remains the same as
the original UPS. Each UPM is rated for a maximum of 300 kVA.
Refer to the
Eaton
®
Power Xpert
®
9395/9395P Integrated Battery Cabinet (Models
1085 and 1085HR) Installation Manual (P-164000580)
for specifics on battery cabinet
usage with the PowerXpert 9395P.
1.4.3
Sync Control
An optional Eaton 9395P Sync Control maintains the critical load outputs of two
separate single module Eaton 9395P UPS systems in synchronization. This option
facilitates the uninterrupted transfer of the load from one load bus to another by
means of transfer switches. The Sync Control is housed in a wall‐mounted panel that
can be located between the UPS units for easy wiring.
Refer to the
Eaton
®
Power Xpert
®
9395P Sync Control Installation and Operation
Manual (P-164000502)
for specifics on battery cabinet usage with the PowerXpert
9395P.
1.4.4
Single-Feed Kit
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a
single-feed configuration. The kit consists of jumpers and bus bar extensions for each
phase, and the hardware required for installation.
Refer to the
Eaton
®
Power Xpert
®
9395/9395P UPS (1000-1200 kVA) Single-Feed Kit
Installation Instructions (P-164000610)
manual for installation instructions.
1.4.5
Distributed Bypass System
There are two types of redundancy: UPS based (based on the number of UPSs) and
UPM based (based on the number of UPMs).
NOTE
All UPSs in the distributed bypass system must contain the same number of UPMs. Mixed UPS kVA
ratings are not permitted.
A distributed bypass UPS system can be installed to provide a capacity and/or
redundant system. This load sharing system provides more capacity than a single
UPS, and can provide backup, depending on the load and configuration.