MISE EN GARDE!
Vérifier que les filtres sont bien secs avant de les réinstaller.
a.
Remove one top screw and two bottom screws securing each UPM section
front panel. Lift the panel straight up to remove it from the panel hanger
bracket at the top of the cabinet.
b.
Remove one top screw and two bottom screws securing each ISBM section
front panel. Lift the panel straight up to remove it from the panel hanger
bracket at the top of the cabinet.
c.
If the UPS is a continuous static switch configuration, unfasten the front
door latch and swing the door open.
d.
Pull the foam filters over the screw heads on the cabinet mounted studs and
remove the filters from the cabinet.
e.
Push the washed or new foam filters over the screw heads on the cabinet
mounted studs until seated against the cabinet.
f.
Reinstall the UPM section front panels removed in Step a and secure with
the retained hardware.
g.
Reinstall the ISBM section front panel removed in Step b and secure with
the retained hardware.
h.
If opened, close the front door and secure the latch.