background image

12

Instruction Manual 

IB015002EN

Effective November 2021

Pow-R-Line CS switchboards 

  

  

EATON

 www.EatonCanada.ca/PRLCS

Current transformers

Switchboards containing metering and monitoring equipment may 

contain current transformers (CTs) integral to the switchboard . 

Ensure that the load side of the CTs are connected or are shorted 

together with terminal block shorting means . Remove shorting 

means for normal CT operation with metering equipment . For 

additional information and instructions, refer to instruction leaflet 

shipped with the switchboard .

Preparing switchboard for insulation/megger testing

 CAUTION

FAILURE TO SHORT OR DISCONNECT DURING SWITCHBOARD TESTING 

WILL RESULT IN FAILURE OF ELECTRONIC COMPONENTS.

Devices installed with control power fusing

Devices, which require control power fusing, can be easily damaged 

beyond repair if not disconnected during the testing phase . 

These devices include, but are not limited to, customer metering 

equipment, electronic breaker trip units, motor operators and 

communication equipment

 WARNING

DISCONNECT POWER AT SOURCE BEFORE REMOVING OR INSTALLING 

FUSES. HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH.

Prior to testing the switchboard, turn off all control power devices 

in the switchboard to prevent damage to components . The control 

power may be turned off by utilizing the control power switch or by 

removing the fuses . Components that use power supplies include 

customer metering and certain breaker accessories and these must 

be isolated before testing .

 CAUTION

FAILURE TO DISCONNECT CONTROL POWER DURING SWITCHBOARD 

TESTING WILL RESULT IN FAILURE OF ELECTRONIC COMPONENTS.

Failure to disconnect control power during switchboard 

testing will result in failure of electronic components and void 

manufacturer’s warranty.

Transient Voltage Surge Suppression (TVSS) and  

Surge Protective Devices (SPD)

Prior to testing the switchboard, disconnect line and neutral 

connections to all TVSS and/or SPD units in the switchboard . Keep 

hardware in a clean and protected environment to guard against 

damage until re-installation

 CAUTION

FAILURE TO DISCONNECT LINE AND NEUTRAL DURING TESTING WILL 

CAUSE THE TVSS AND SPD SURGE PROTECTION SYSTEM TO FAIL AND 

WILL VOID THE WARRANTY ON THE DEVICE.

Failure to disconnect line and neutral during testing will cause 

the TVSS and SPD surge protection system to fail and will 

void the warranty on the device. After testing, re-install all 

connections. 

Pre-energizing switchboard insulation testing

Exercise extreme care to prevent the equipment from being 

connected to the power source while tests are being conducted.

Prior to energizing the switchboard, perform a Megger or DC test 

of the switchboard’s insulation . With the neutral isolated from the 

ground and the switches and/or circuit breakers open, conduct 

electrical insulation resistance tests from phase to phase, phase 

to ground, phase to neutral, and neutral to ground . Retain results 

for use to compare to results produced in the future . A form for 

recording test results is provided in the Appendix of this document . 

Prior to testing, remove all control power fusing and connections to 

products, which will be damaged in this test . See above .

 WARNING

TO PREVENT DAMAGE TO GROUND FAULT CONTROL CIRCUITS, 

METERING CIRCUITS, OR OTHER CONTROL CIRCUITS WHEN 

MEGGERING SWITCHBOARD, ISOLATE CIRCUITS FROM SWITCHBOARD 

SYSTEM BEFORE BEGINNING THE MEGGER OPERATION. BE SURE TO 

RECONNECT THOSE CIRCUITS AFTER MEGGER TESTS ARE COMPLETED. 

 

NOTE: SOME GROUND FAULT CIRCUITS MAY NOT BE FUSED, 

THEREFORE ISOLATION OF THOSE CIRCUITS REQUIRES DISCONNECTING 

WIRING FROM BUS BARS.

DO NOT USE AC dielectric testing.

 WARNING

DO NOT USE AC DIELECTRIC/MEGGER TESTING.

Test resulting in readings at or above 1 megaohm is satisfactory . 

If failed to comply with these procedures . Eaton is not liable for 

damage

Post-testing

After testing, and with the switchboard de-energized, reconnect all 

devices, control fusing and disconnects removed prior to testing . 

Re-attach Transient Voltage Surge Suppressors (TVSS) and Surge 

Protective Devices (SPD) .

Securing the switchboard

Re-install all side covers, deadfront plates, doors and trim parts 

on the switchboard using hardware supplied by the manufacturer . 

Take caution that conductors are not pinched between parts when 

installing the deadfront, cover plates, side sheets and filler plates . 

All parts should be aligned and secured when installed . Do not leave 

holes or gaps in the deadfront construction . Clean up any debris in 

and around the switchboard .

Summary of Contents for Pow-R-Line CS

Page 1: ...afety measures 2 Pre installation receiving handling and storage 3 Pre installation preparation 5 Considerations for seismic qualified installations 5 Electrical connection of switchboard sections 7 E...

Page 2: ...ARNING WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN DEATH OR SERIOUS INJURY CAUTION CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED C...

Page 3: ...d until it has been moved into its final installation position Handling WARNING SWITCHBOARD IS TOP HEAVY USE CARE IN HANDLING Switchboards are top heavy Switchboard sections may weigh over 2000 pounds...

Page 4: ...PASS ROPES OR CABLES THROUGH LIFT HOLES USE SLINGS WITH SAFETY HOOKS OR SHACKLES SPANNER BAR CHANNEL BLOCKS SWITCHBOARD SHIPPING SKID Figure 5 Bottom lifting with sling rigging Forklifts A forklift ma...

Page 5: ...the finished grade flooring See Figure 7 Conduits must be installed in conduit area shown to ensure compliance with CEC wire bending space requirements ote N Conduit areas may vary in each section of...

Page 6: ...om any wall or building structure For other required clearances including rear connected switchboard refer to the Canadian Electrical Code CEC clearances When unpacking the switchboard exercise care n...

Page 7: ...horizontally through multiple section switchboards Depending on the configuration and alignment of the switchboard the splice plates used for the main cross bus may vary These plates may either be fl...

Page 8: ...The Canadian Electrical Code restricts the field installation of conductors that run horizontally through switchboard vertical sections Refer to the CEC for specifics When there is a shipping split be...

Page 9: ...Conductor must be stripped without damage to the conductor strands Bare strands should be of equal length flush on the end cut Do not strip off more insulation than needed Exposure of bare conductor o...

Page 10: ...on points to ensure that there is no blockage or debris Remove all debris if present 6 Verify all field bus and wire connections have the proper torque per instructions on the switchboard and on compo...

Page 11: ...drawings and electrical construction drawings for usage and placement within the switchboard Ground fault protection may be installed integral to over current device s or as a separate system Separat...

Page 12: ...HE TVSS AND SPD SURGE PROTECTION SYSTEM TO FAIL AND WILL VOID THE WARRANTY ON THE DEVICE Failure to disconnect line and neutral during testing will cause the TVSS and SPD surge protection system to fa...

Page 13: ...s and loads 4 Beginning with the main s turn ON each overcurrent device Maintenance It is essential to maintain the equipment in satisfactory condition To ensure continued quality service a systematic...

Page 14: ...and other components Damage to insulation and other surface materials can occur Do Not Use Compressed Air in cleaning Switchboard insulation resistance testing Maintenance after cleaning After cleani...

Page 15: ...pinched or damaged insulation Ventilation Check all grills and ventilation ports for obstructions and accumulations of dirt Clean ventilation ports if necessary For switchboards installed outdoors ins...

Page 16: ...ly 250 watts per vertical section for a sufficient period of time until the moisture disappears then remove all heat sources and materials used for drying Inspect for damage to components and any corr...

Page 17: ...testing and inspection logs Refer to the Maintenance section of this document on page 13 for detailed information DANGER HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH DE ENERGIZE BOARD PRIOR TO...

Page 18: ...nd B Ground C Ground Date All overcurrent devices closed Phase to phase connections Phase to ground connections Neutral ground connection A B A C B C A Ground B Ground C Ground Notes Date All overcurr...

Page 19: ...ntrol wiring Clean ventilation Date Checklist Notes and actions taken Cleaning Bus and cable connections Insulation inspection Overcurrent device inspection Meters Controllers Surge protective devices...

Page 20: ...ca 2021 Eaton All Rights Reserved Printed in Canada Publication No IB015002EN November 2021 Eaton is a registered trademark All other trademarks are property of their respective owners Pow R Line CS s...

Reviews: