background image

10

Instruction Manual 

IB015002EN

Effective November 2021

Pow-R-Line CS switchboards 

  

  

EATON

 www.EatonCanada.ca/PRLCS

Other requirements for rear-connected switchboards

On systems that require short circuit current ratings above 10,000 

amperes rms, Cable Bracing may be required to restrict cable 

movement . Lashing and lacing cables accomplish thi . 

Pre-energizing procedures and inspection

Before energizing any switchboard, perform a comprehensive 

inspection to make certain that the switchboard is ready to be 

energized . This includes the following steps:

1. 

Verify that the switchboard is not energized .

2. 

Visually inspect the switchboard and remove all foreign 

materials, such as, tools, scraps of wire and other debris from all 

switchboard sections .

3. 

Remove and discard all packing materials and temporary shipping 

braces from the switchboard .

4. 

Any accumulation of dust and dirt should be removed with a 

vacuum cleaner . Use a lint-free cloth to remove dust and dirt 

on other surfaces . Never use compressed air as this may blow 

contaminants into electrical and/or electronic components . 

Never use solvents or other chemicals to clean surfaces or 

components .

5. 

Visually inspect all ventilation points to ensure that there is no 

blockage or debris . Remove all debris, if present .

6. 

Verify all field bus and wire connections have the proper torque 

per instructions on the switchboard and on components .

7. 

All factory connections are made utilizing calibrated power 

tools . However, vibrations do occur in transit and handling . 

Verify factory connections by checking at least 10% of the total 

factory connections for tightness . If this spot check reveals 

loose connections, proceed to check all factory connections . 

These connections include bus hardware connections, circuit 

breaker and switch terminals, contactors, metering and other 

connections, including the incoming terminals .

8. 

Visually inspect switchboard insulators, bus bar and conductors 

for damage . DO NOT ENERGIZE IF DAMAGE IS FOUND . Contact 

Eaton .

9. 

If fusible switch type overcurrent devices are used, verify proper 

fusing has been selected and installed . Eaton does not typically 

supply switchboards with these fuses .

Overcurrent devices

Overcurrent devices are typically shipped in either the open (OFF) 

or “tripped” position . Manually close, and then open these devices 

to ensure they are functioning properly . At the completion of this 

process, be sure that the over-current device is in the “OFF” or 

“tripped” position .
Inspect overcurrent devices for any visible damage . If damage is 

found, DO NOT ENERGIZE the switchboard . Contact Eaton .

Summary of Contents for Pow-R-Line CS

Page 1: ...afety measures 2 Pre installation receiving handling and storage 3 Pre installation preparation 5 Considerations for seismic qualified installations 5 Electrical connection of switchboard sections 7 E...

Page 2: ...ARNING WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED CAN RESULT IN DEATH OR SERIOUS INJURY CAUTION CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED C...

Page 3: ...d until it has been moved into its final installation position Handling WARNING SWITCHBOARD IS TOP HEAVY USE CARE IN HANDLING Switchboards are top heavy Switchboard sections may weigh over 2000 pounds...

Page 4: ...PASS ROPES OR CABLES THROUGH LIFT HOLES USE SLINGS WITH SAFETY HOOKS OR SHACKLES SPANNER BAR CHANNEL BLOCKS SWITCHBOARD SHIPPING SKID Figure 5 Bottom lifting with sling rigging Forklifts A forklift ma...

Page 5: ...the finished grade flooring See Figure 7 Conduits must be installed in conduit area shown to ensure compliance with CEC wire bending space requirements ote N Conduit areas may vary in each section of...

Page 6: ...om any wall or building structure For other required clearances including rear connected switchboard refer to the Canadian Electrical Code CEC clearances When unpacking the switchboard exercise care n...

Page 7: ...horizontally through multiple section switchboards Depending on the configuration and alignment of the switchboard the splice plates used for the main cross bus may vary These plates may either be fl...

Page 8: ...The Canadian Electrical Code restricts the field installation of conductors that run horizontally through switchboard vertical sections Refer to the CEC for specifics When there is a shipping split be...

Page 9: ...Conductor must be stripped without damage to the conductor strands Bare strands should be of equal length flush on the end cut Do not strip off more insulation than needed Exposure of bare conductor o...

Page 10: ...on points to ensure that there is no blockage or debris Remove all debris if present 6 Verify all field bus and wire connections have the proper torque per instructions on the switchboard and on compo...

Page 11: ...drawings and electrical construction drawings for usage and placement within the switchboard Ground fault protection may be installed integral to over current device s or as a separate system Separat...

Page 12: ...HE TVSS AND SPD SURGE PROTECTION SYSTEM TO FAIL AND WILL VOID THE WARRANTY ON THE DEVICE Failure to disconnect line and neutral during testing will cause the TVSS and SPD surge protection system to fa...

Page 13: ...s and loads 4 Beginning with the main s turn ON each overcurrent device Maintenance It is essential to maintain the equipment in satisfactory condition To ensure continued quality service a systematic...

Page 14: ...and other components Damage to insulation and other surface materials can occur Do Not Use Compressed Air in cleaning Switchboard insulation resistance testing Maintenance after cleaning After cleani...

Page 15: ...pinched or damaged insulation Ventilation Check all grills and ventilation ports for obstructions and accumulations of dirt Clean ventilation ports if necessary For switchboards installed outdoors ins...

Page 16: ...ly 250 watts per vertical section for a sufficient period of time until the moisture disappears then remove all heat sources and materials used for drying Inspect for damage to components and any corr...

Page 17: ...testing and inspection logs Refer to the Maintenance section of this document on page 13 for detailed information DANGER HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH DE ENERGIZE BOARD PRIOR TO...

Page 18: ...nd B Ground C Ground Date All overcurrent devices closed Phase to phase connections Phase to ground connections Neutral ground connection A B A C B C A Ground B Ground C Ground Notes Date All overcurr...

Page 19: ...ntrol wiring Clean ventilation Date Checklist Notes and actions taken Cleaning Bus and cable connections Insulation inspection Overcurrent device inspection Meters Controllers Surge protective devices...

Page 20: ...ca 2021 Eaton All Rights Reserved Printed in Canada Publication No IB015002EN November 2021 Eaton is a registered trademark All other trademarks are property of their respective owners Pow R Line CS s...

Reviews: