Parameter setting
35
11/04 MN01219002Z-EN
Parameter setting
Input menu
Parameters for the circuit-breaker and the DMI are assigned
in the Input menu. This menu is the most complex one in the
DMI on account of its wide range of setting and parameter
assignment options.
Password setting/changing
Entries cant be input unless the password has been entered
correctly. A value between 0000 and 9999 must be entered
as a password.
You can set or change a password via the Special menu
(
a
section “Special menu”, Page 16).
X
Call up the Special menu via
ALT
and
DEL
.
X
Select Password using the cursor buttons
Í
or
Ú
.
X
Confirm your selection by pressing
OK
.
Caution!
The Input menu is password protected since changes to
the parameters can affect the entire system, and may in
the event of a fault cause material damage and possibly
serious injury to persons.
h
In order to prevent unauthorised modifications, the DMI
switches to the main menu if correct password entry does
not take place within 30 s. The entry level is then only
accessible when the correct password is entered again.
h
Forgotten the password?
You must now write a new
parameter set with the required password into the DMI
using the PC user interface. In order to retain the current
configuration, transfer the current configuration to the PC
interface with “DMI upload” and save it if necessary. The
password can then be changed and the new setting can be
transferred back to the DMI with “DMI download“.