PROFIBUS-DPV1 functions
151
11/04 MN01219002Z-EN
Format and meaning of the object data content
The following table displays the address location and the
meaning of the data content of the object. Furthermore, it
provides an example of how the data content can be
accessed by the application with the aid of the example
variable.
Table 35: Address location and meaning of the object data
content
Variable access
(example)
Data position
Meaning
Octet 1
LS_DMI_Com_Status[1]
Bit 0
NZM with new serial number recognised and
stop mode active
LS_DMI_Com_Status[2]
Bit 1
Parameters in DMI (parameters used) and NZM
(locally set parameters) differ
LS_DMI_Com_Status[3]
Bit 2
Motor-starter function in DMI parameterized,
which are not supported by the connected NZM
Bit 3 to Bit 4
Not used
LS_DMI_Com_Status[6]
Bit 5
After initialization of the interface until a CB-
identity (circuit breaker identity) or PC identity
have been recognised when a connection is
being established.
LS_DMI_Com_Status[7]
Bit 6
After initialization of the interface until an
identity block has been correctly received when
a connection is being established
LS_DMI_Com_Status[8]
Bit 7
After initialization of the interface until the first
transfer command has been correctly received
when a connection is being established
Octet 2
Bit 0 to 7
Not used
h
The meaning is relevant when the respective Bit is set.