PROFIBUS-DPV0 functions
105
11/04 MN01219002Z-EN
Motor state
Is set if the Motor “ON” bit, motor
anticlockwise rotation or motor
clockwise rotation is set
Motor-starter function is
parameterized in DMI
Motor “ON”
0
1
Motor is switched off
Motor is switched on
Output 0 has been parameterized
to “direct-on-line starter” or
outputs 0, 2 and 3 have been
parameterized for “star-delta
starter”
Not used
No information for evaluation
–
Overload warning
At least one phase current has exceeded
the overload 1 limit (
I
r
= 100 %)
–
Ready to switch on
1
The circuit-breaker is switched off
(not tripped)
–
Star configuration
0
1
The motor will not be operated in
star configuration
The motor is operated in star
configuration
Outputs 0, 2, 3 have been
parameterized for “star-delta
starter” or
the outputs 0, 1, 2 and 3 have
been parameterized for “star-
delta-reversing starter”
Trip cause
(Release reason)
000
001
010
011
100
101
110
no trip
I
r
I
i
I
sd
I
dn
selectivity, communication fault,
over-temperature hardware fault
neutral pole overcurrent
–
h
The delta mode, motor “ON”, motor anticlockwise, motor
clockwise, motor state and star mode data content are
compiled from the control signals of the DMI outputs to
which the contactor relays for motor control are connected
(
a
section “Motor starter”, Page 44). They therefore
only conditionally reflect the state of the motor control.
Designation
Meaning
Precondition