PROFIBUS-DPV1 functions
185
11/04 MN01219002Z-EN
Object compilation B
This object contain a ready-made compilation of the data
content of the following objects:
• Parameters used by circuit-breaker,
• Circuit-breaker locally set parameters.
This object is a read only object. It can be accessed by class 1
and/or a class 2 DPV1 master.
Intended usage
Use this object if you want to obtain information about the
data content of the contained objects with a read operation.
Note all the information contained in the descriptions of the
individual objects which are included.
Octet 31
1)
Fault states
LS_Status[49]
Bit 0
NZM fault: A/D convertor
LS_Status[50]
Bit 1
NZM fault: Signal processing
LS_Status[51]
Bit 2
NZM fault: Convertor block
LS_Status[52]
Bit 3
NZM fault: EEPROM
LS_Status[53]
Bit 4
NZM plug in module 1 fault
LS_Status[54]
Bit 5
NZM plug in module 2 fault
LS_Status[55]
Bit 6
NZM plug in module 3 fault
LS_Status[56]
Bit 7
NZM plug in module 4 fault
1) The meaning is relevant when the respective Bit is set.