![background image](http://html1.mh-extra.com/html/eaton/iq-100-series/iq-100-series_user-and-installation-manual_3829319018.webp)
IQ 100 Series (130/140/150) Meter
Mechanical Installation
18 User and Installation Manual IM02601003E-July 2010 www.eaton.com
ANSI Installation Steps
1.
Insert 4 threaded rods by hand into the back of meter. Twist until secure.
2.
Slide ANSI 12 Mounting Gasket onto back of meter with rods in place.
3.
Slide meter with Mounting Gasket into panel.
4.
Secure from back of panel with lock washer and nut on each threaded rod.
Use a small wrench to tighten. Do not overtighten.
The maximum installation torque is
0.4 Newton-Meter.
NEMA 12 Mounting Gasket
Threaded Rods
Lock Washer and Nut