IQ 100 Series (130/140/150) Meter
Appendix B: Modbus Map
Description
1
Format
Range
6
Units or
Resolution
Comments
#
Reg
Modbus Address
Hex
Decimal
0FA9 - 0FA9
4010 - 4010
Reserved
1
0FAA - 0FAA
4011 - 4011
Reserved
1
0FAB - 0FAB
4012 - 4012
Reserved
1
0FAC - 0FAC
4013 - 4013
Reserved
1
0FAD - 0FAD
4014 - 4014
Reserved
1
0FAE - 0FAE
4015 - 4015
Reserved
1
0FAF - 0FAF
4016 - 4016
Reserved
1
0FB0 - 0FB0
4017 - 4017
Reserved
1
0FB1 - 0FB8
4018 - 4025
Reserved
8
0FB9 - 0FBC
4026 - 4029
Reserved
4
0FBD - 0FC4
4030 - 4037
Reserved
8
0FC5 - 0FC8
4038 - 4041
Reserved
4
Block Size:
42
read-only
1003 - 1003
4100 - 4100
Phase A Current
SINT16
-1800 to +1800
0.1 degree
1
1004 - 1004
4101 - 4101
Phase B Current
SINT16
-1800 to +1800
0.1 degree
1
1005 - 1005
4102 - 4102
Phase C Current
SINT16
-1800 to +1800
0.1 degree
1
1006 - 1006
4103 - 4103
Angle, Volts A-B
SINT16
-1800 to +1800
0.1 degree
1
1007 - 1007
4104 - 4104
Angle, Volts B-C
SINT16
-1800 to +1800
0.1 degree
1
1008 - 1008
4105 - 4105
Angle, Volts C-A
SINT16
-1800 to +1800
0.1 degree
1
Block Size:
6
read-only
1387 - 1387
5000 - 5000
Meter Status
UINT16
bit-mapped
--exnpch ssssssss
exnpch = EEPROM block OK flags
(e=energy, x=max, n=min, p=programmable
settings, c=calibration, h=header),
ssssssss = state (1=Run, 2=Limp, 10=Prog
Set Update via buttons, 12=Prog Set
Update via COM2)
1
1388 - 1388
5001 - 5001
Reserved
1
1389 - 138A
5002 - 5003
Time Since Reset
UINT32
0 to 4294967294
4 msec
wraps around after max coun
2
Block Size:
4
write-only
4E1F - 4E1F
20000 - 20000
Reset Max/Min Blocks
UINT16
password
5
1
4E20 - 4E20
20001 - 20001
Reset Energy Accumulators
UINT16
password
5
1
Status Block
Phase Angle Block
14
Commands Section
4
Resets Block
9
User and Installation Manual