IQ 100 Series ((130/140/150) Meter
Overview & Specifications
User and Installation Manual IM02601003E - July 2010 www.eaton.com 15
Isolation
·
All Inputs and Outputs are galvanically isolated to 2500 Vac
Environmental Rating
·
Storage:
(-40 to +85)
0
C
·
Operating:
(-20 to +70)
0
C
·
Humidity:
to 95% RH Non-condensing
·
Faceplate Rating:
NEMA12 (Water Resistant), Mounting Gasket Included
Measurement Methods
·
Voltage, Current:
True RMS
·
Power:
Sampling at 400+ Samples per Cycle on All Channels
Measured Readings Simultaneously
·
A/D Conversion:
6 Simultaneous 24 bit Analog to Digital Converters
Update Rate
·
Watts, VAR and VA:
100 milliseconds (Ten times per second)
·
All other parameters:
1 second
Communication Format
1. Optional RS485 and KYZ Pulse Output through Back Plate (Standard with Transducer-
only version)
·
Protocols:
Modbus RTU, Modbus ASCII
·
Com Port Baud Rate:
9600 to 57,600 b/s
·
Com Port Address:
001-247
·
Data Format:
8 Bit, No Parity
·
IQ 100 Series Transducer Default Initial Communication Baud 9600 (see Chapter 4)
Mechanical Parameters
·
Dimensions:
(H4.85 x W4.82 x L4.25) inches, (H123.2 x W123.2 x
L105.4) mm
Mounts in 92mm square DIN or ANSI C39.1, 4” Round Cut-out
·
Weight:
2 pounds, 0.907kg (ships in a 6”/152.4mm cube container)