IQ 100 Series (130/140/150) Meter
Appendix B: Modbus Map
Description
1
Format
Range
6
Units or
Resolution
Comments
#
Reg
Modbus Address
Hex
Decimal
0BCD - 0BCE
3022 - 3023
Negative Watts, 3-Ph, Minimum Avg Demand
FLOAT
0 to +9999 M
watts
2
0BCF - 0BD0
3024 - 3025
Negative VARs, 3-Ph, Minimum Avg Demand
FLOAT
0 to +9999 M
VARs
2
0BD1 - 0BD2
3026 - 3027
VAs, 3-Ph, Minimum Avg Demand
FLOAT
-9999 M to +9999 M
VAs
2
0BD3 - 0BD4
3028 - 3029
Positive Power Factor, 3-Ph, Minimum Avg Demand
FLOAT
-1.00 to +1.00
none
2
0BD5 - 0BD6
3030 - 3031
Negative Power Factor, 3-Ph, Minimum Avg Demand
FLOAT
-1.00 to +1.00
none
2
0BD7 - 0BD8
3032 - 3033
Frequency, Minimum
FLOAT
0 to 65.00
Hz
2
Block Size:
34
read-only
0C1B - 0C1C
3100 - 3101
Volts A-N, Maximum
FLOAT
0 to 9999 M
volts
2
0C1D - 0C1E
3102 - 3103
Volts B-N, Maximum
FLOAT
0 to 9999 M
volts
2
0C1F - 0C20
3104 - 3105
Volts C-N, Maximum
FLOAT
0 to 9999 M
volts
2
0C21 - 0C22
3106 - 3107
Volts A-B, Maximum
FLOAT
0 to 9999 M
volts
2
0C23 - 0C24
3108 - 3109
Volts B-C, Maximum
FLOAT
0 to 9999 M
volts
2
0C25 - 0C26
3110 - 3111
Volts C-A, Maximum
FLOAT
0 to 9999 M
volts
2
0C27 - 0C28
3112 - 3113
Amps A, Maximum Avg Demand
FLOAT
0 to 9999 M
amps
2
0C29 - 0C2A
3114 - 3115
Amps B, Maximum Avg Demand
FLOAT
0 to 9999 M
amps
2
0C2B - 0C2C
3116 - 3117
Amps C, Maximum Avg Demand
FLOAT
0 to 9999 M
amps
2
0C2D - 0C2E
3118 - 3119
Positive Watts, 3-Ph, Maximum Avg Demand
FLOAT
0 to +9999 M
watts
2
0C2F - 0C30
3120 - 3121
Positive VARs, 3-Ph, Maximum Avg Demand
FLOAT
0 to +9999 M
VARs
2
0C31 - 0C32
3122 - 3123
Negative Watts, 3-Ph, Maximum Avg Demand
FLOAT
0 to +9999 M
watts
2
0C33 - 0C34
3124 - 3125
Negative VARs, 3-Ph, Maximum Avg Demand
FLOAT
0 to +9999 M
VARs
2
0C35 - 0C36
3126 - 3127
VAs, 3-Ph, Maximum Avg Demand
FLOAT
-9999 M to +9999 M
VAs
2
0C37 - 0C38
3128 - 3129
Positive Power Factor, 3-Ph, Maximum Avg Demand
FLOAT
-1.00 to +1.00
none
2
0C39 - 0C3A
3130 - 3131
Negative Power Factor, 3-Ph, Maximum Avg Demand
FLOAT
-1.00 to +1.00
none
2
0C3B - 0C3C
3132 - 3133
Frequency, Maximum
FLOAT
0 to 65.00
Hz
2
Block Size:
34
read-only
0F9F - 0F9F
4000 - 4000
Reserved
UINT16
0 to 9999, or 65535
0.1%
1
0FA0 - 0FA0
4001 - 4001
Reserved
UINT16
0 to 9999, or 65535
0.1%
1
0FA1 - 0FA1
4002 - 4002
Reserved
UINT16
0 to 9999, or 65535
0.1%
1
0FA2 - 0FA2
4003 - 4003
Reserved
UINT16
0 to 9999, or 65535
0.1%
1
0FA3 - 0FA3
4004 - 4004
Reserved
1
0FA4 - 0FA4
4005 - 4005
Reserved
1
0FA5 - 0FA5
4006 - 4006
Reserved
1
0FA6 - 0FA6
4007 - 4007
Reserved
1
0FA7 - 0FA7
4008 - 4008
Reserved
1
0FA8 - 0FA8
4009 - 4009
Reserved
1
Primary Maximum Block (IEEE Floating Point)
Reserved Block
7, 13
User and Installation Manual
IM02601003E -
December
2009
MM-3