IQ 100 Series (130/140/150) Meter
Overview &Specifications
16 User and Installation Manual IM02601003E-July 2010 www.eaton.com
Compliance
UL Listing: USL/CNL E185559
•
IEC 687 (0.5% Accuracy)
•
ANSI C12.20 (0.5% Accuracy)
•
ANSI (IEEE) C37.90.1 Surge Withstand
•
ANSI C62.41 (Burst)
•
IEC1000-4-2: ESD
•
IEC1000-4-3: Radiated Immunity
•
IEC1000-4-4: Fast Transient
•
IEC1000-4-5: Surge Immunity
•
Accuracy
Meter Accuracy by Measured Parameter
Measured Parameters
Accuracy % of Reading*
Display Range
Voltage L-N
0.25%
0-9999 V or kV Autoscale
Voltage L-L
0.25%
0-9999 V or kV Autoscale
Current Phase
0.25%
0-9999 V or kV Autoscale
Current Neutral (Calculated)
2.0% F.S.
0-9999 V or kV Autoscale
+/- Watts
0.5%
0-9999 Watts, kWatts, MWatts
+/- Wh
0.5%
5 to 8 Digits Programmable
+/- VARs
0.5%
0-9999 VARs, kVARs, MVARs
+/- VARh
0.5%
5 to 8 Digits Programmable
VA
0.5%
0-9999 VA, kVA, MVA
VAh
0.5%
5 to 8 Digits Programmable
PF
0.5%
+/- 0.5 to 1.0
Frequency
+/- 0.01 Hz
45 to 65 Hz
% of Load Bar
1-120%
10 Segment Resolution Scalable
*Accuracy stated for 5Amp secondary WYE or Delta connections. For 1Amp secondary or 2.5 element
connections, add 0.1% of Full Scale + 1 digit to accuracy specification.