Hardware Overview
The IQ 100 (IQ 130/140/150) is a multifunction power meter designed to be used in electrical substa
-
tions, panel boards and as a power meter for OEM equipment. The unit provides multifunction measure
-
ment of most electrical parameters.
The unit is designed with advanced meaurement capabilities, allowing it to achieve high performance
accuracy. The IQ 100 meter is specified as a 0.5% class energy meter for billing applications as well as
a highly accurate panel indication meter.
The IQ 100 meter provides a host of additional capabilities, including optional RS485 Modbus.
IQ 100 meter features that are detailed in this manual are as follows:
0.5% Class Revenue Certifiable Energy and Demand (IQ 140/150) Metering
•
Meets ANSI C12.20 (0.5%)
•
Multifunction Measurement including Voltage, Current, Power, Frequency, Energy, etc.
•
Field Upgrade without Removing Installed Meter
•
Percentage of Load Bar for Analog Meter Perception
•
Easy to Use Faceplate Programming
•
The IQ 100 Series meter is available in two configurations: meter/transducer and transducer only.
IQ 100 Series Meter / Digital Transducer
Meter and transducer in one compact unit. Features an optional RS485 and KYZ Pulse Output, and can
be programmed using the faceplate of the meter. ANSI or DIN mounting may be used.
IQ 100 Series Digital Transducer
A Digital Transducer only unit providing RS485 communication via Modbus RTU or Modbus ASCII proto
-
cols. The unit is designed to install using DIN Rail Mounting (see instructions on page 20).
Voltage and Current Inputs
Universal Voltage Inputs
Voltage Inputs allow measurement to 416 Volts Line-to-Neutral and 721 Volts Line-to-Line. This insures
proper meter safety when wiring directly to high voltage systems. One unit will perform to specification
on 69 Volt, 120 Volt, 230 Volt, 277 Volt, 277 Volt and 347 Volt power systems.