DC Cabling
Copyright © 2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-82B May 2011
19
The following table shows the minimum size cable and typical UL-listed crimp lug that must be
used for the telecom earth cable.
Conductor:
Copper, stranded single-core
Temperature rating:
194°F (90°C) minimum
Cable size:
0000 AWG
Metric cable size (equivalent min.): 95 mm
2
Strip length:
1-1/8 inch (29mm)
Crimp lug:
YA28L-BOX*
Crimping tool:
MY29-11 (dieless)*
* Part numbers are for FCI-BURNDY® products. In US/Canada use these parts or equivalent UL-Listed
crimp lugs. In other countries use equivalent parts.
Fit or Remove Low Voltage Disconnects
Ignore this task if no changes are required to the low voltage disconnects (LVDs).
Step 1 - Fit or remove the battery disconnect LVD (if required)
DCM2000 distribution module (rear view)
Battery LVD contactor.
Contactor bus retaining bolts (2 x M10).
Contactor mounting screws and isolators (4 x
M4).
Contactor bus nuts (4 x M12).
Contactor bus retaining nuts (2 x M10).
Link bar (in place of contactor).