Data-Voice-Video 3G Power Solutions (UL-Listed Models)
22
Copyright © 2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-82B May 2011
Load Cables and Circuit Breakers
Before proceeding with cable termination remove switch off all circuit breakers.
Always check that the battery cables have been terminated to the correct system polarity BEFORE
connecting the batteries or closing the battery disconnect device.
Connecting batteries to the system with incorrect system polarity will void all warranty claims.
Refer to the Specifications on page
for the maximum load currents.
Front cover (hinged, screw-fixed).
Circuit breaker cover.
Up to 20 circuit breakers (dependent on ratings).
Space required between some circuit breakers. Alarm
signal if circuit breaker is electrically tripped only.
Live cable connection plates, single, double or triple
to suit circuit breakers.
Live terminal insulators (1-pole, 2-pole or 3-pole to
suit circuit breakers).
Common bar.
Step 1 - Access circuit breakers
1
Open the hinged front cover.
2
Switch off all circuit breakers.
3
Undo and remove the circuit breaker cover.
4
If necessary, remove cabinet side panels for rear/top access.