Data-Voice-Video 3G Power Solutions (UL-Listed Models)
28
Copyright © 2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-82B May 2011
Battery Types
To maintain the UL certification, suitable UL certified batteries must be fitted. The table below
gives some suitable battery types.
Manufacturer
Part number
Manufacturer's recommended terminal
torque
Haze Battery USA
TEL105F
5.0 - 6.9 Nm (44 - 62 inch-pounds)
Haze Battery USA
TEL150F
5.0 - 6.9 Nm (44 - 62 inch-pounds)
Haze Battery Shenzhen
HZB12-100FA
5.0 - 7.0 Nm (44 - 62 inch-pounds)
Haze Battery Shenzhen
HZB12-150FA
5.0 - 7.0 Nm (44 - 62 inch-pounds)
Northstar
NSB100FT
8.0 Nm (71 inch-pounds)
East Penn
12AVR100ET
6.3 - 7.3 Nm (55 - 65 inch-pounds)
Installing the Batteries
Always check that the battery cables have been terminated to the correct system polarity
BEFORE connecting the batteries or closing the battery disconnect device.
Connecting batteries to the system with incorrect system polarity will void all warranty
claims.
See Warnings on page
The following are recommended Battery Installation Practices. These supplement any specific
installation instructions from the battery manufacturer.
General
Do not wear a synthetic dust-coat or overalls. Synthetic fabrics can hold a static electric
charge, creating sparks during discharge.
Remove rings, wristwatch and other metal jewelry that might be exposed to battery
terminals, before installing batteries.
Only use a clean soft damp cloth for cleaning the batteries. Do not use cleaning detergents
or chemicals.
Flooded cell and VRLA lead acid batteries can emit explosive gases and must be installed
with adequate ventilation. Refer to the battery manufacturer or supplier for advice on
minimum ventilation levels.
Ensure that the battery strings are disconnected from the dc power system, by switching off
all battery circuit breakers or removing all battery fuses.
Unpacking and Inspecting the Batteries
Unpack the batteries and inspect them carefully for leaks, corrosion and possible damage.
Report any damage or other battery related problems immediately to the battery supplier.
Do not remove the factory-fitted transit insulation covers from the batteries until access to
the battery terminals is required.