27
Modbus TCP On-Board communications
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Process data
The process data fields are used to control the drive (e.g.,
Run, Stop, Reference, Fault Reset) and to quickly read actual
values (e.g., Output frequency, Output current, Fault code).
The fields are structured as follows.
Table 51. Process data slave
→
master (max. 22 bytes)
ID
Modbus register
Group
Range/Type
2101
32101, 42101
FB Status Word
Binary coded
2102
32102, 42102
FB General Status Word Binary coded
2103
32103, 42103
FB Actual Speed
0–100.00%
2104
32104, 42104
FB Process Data Out 1
2105
32105, 42105
FB Process Data Out 2
2106
32106, 42106
FB Process Data Out 3
2107
32107, 42107
FB Process Data Out 4
2108
32108, 42108
FB Process Data Out 5
2109
32109, 42109
FB Process Data Out 6
2110
32110, 42110
FB Process Data Out 7
2111
32111, 42111
FB Process Data Out 8
Table 52. Process data master
→
slave (max. 22 bytes)
ID
Modbus register
Group
Range/Type
2001
32001, 42001
FB Control Word
Binary coded
2002
32002, 42002
FB General Control Word Binary coded
2003
32003, 42003
FB Speed Reference
0–100.00%
2004
32004, 42004
FB Process Data In 1
Integer 16
2005
32005, 42005
FB Process Data In 2
Integer 16
2006
32006, 42006
FB Process Data In 3
Integer 16
2007
32007, 42007
FB Process Data In 4
Integer 16
2008
32008, 42008
FB Process Data In 5
Integer 16
2009
32009, 42009
FB Process Data In 6
Integer 16
2010
32010, 42010
FB Process Data In 7
Integer 16
2011
32011, 42011
FB Process Data In 8
Integer 16
The use of process data depends on the application. In a
typical situation, the device is started and stopped with the
ControlWord (CW) written by the Master and the Rotating
speed is set with Reference (REF). With PD1–PD8 the device
can be given other reference values (e.g., Torque reference).
With the StatusWord (SW) read by the Master, the status
of the device can be seen. Actual Value (ACT) and PD1–PD8
show the other actual values.
Process data in
This register range is reserved for the control of the VFD.
Process Data In is located in range ID 2001–2099. The
registers are updated every 10 ms. See table below.
Table 53. Fieldbus basic input table
ID
Modbus register
Group
Range/Type
2001
32001, 42001
FB Control Word
Binary coded
2002
32002, 42002
FB General Control Word Binary coded
2003
32003, 42003
FB Speed Reference
0–100.00%
2004
32004, 42004
FB Process Data In 1
Integer 16
2005
32005, 42005
FB Process Data In 2
Integer 16
2006
32006, 42006
FB Process Data In 3
Integer 16
2007
32007, 42007
FB Process Data In 4
Integer 16
2008
32008, 42008
FB Process Data In 5
Integer 16
2009
32009, 42009
FB Process Data In 6
Integer 16
2010
32010, 42010
FB Process Data In 7
Integer 16
2011
32011, 42011
FB Process Data In 8
Integer 16