33
EtherNet/IP On-Board communications
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Figure 19. MNdule and neowNrk soaous
Module Status
Network Status
Module status indications
Represents the state of the drive.
Table 66. MNdule soaous LED descripoiNn
Indicator state
Summary
Meaning
Steady off
No power
No power is supplied to the PowerXL.
Steady green
Device operational
PowerXL is operating correctly.
Flashing green
Standby
PowerXL has not been configured.
Flashing red
Minor fault
PowerXL has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady red
Major fault
PowerXL has detected a non-recoverable major fault.
Flashing green/red
Self-test
PowerXL is performing its power on self test.
Network status indications
Represents the state of the Ethernet port network interface.
Table 67. NeowNrk soaous LED descripoiNn
Indicator State
Summary
Meaning
Steady off
Not powered, no IP address
PowerXL is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing green
No connections
An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady green
Connected
At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing red
Connection timeout
PowerXL is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady red
Duplicate IP address
PowerXL has detected a Duplicate IP.
Flashing green/red
Self-test
PowerXL is performing its power on self test.
Flash rate is 1 flash per second.