71
BACnet MS/TP—On-Board communication
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Figure 33. RS-485 Bus oerminaoiNn seoup
BACnet MS/TP bus termination
Figure 34. BACneo bus oerminaoiNn
7.
Remount the AC drive cover.
Noee:
N
When planning the cable runs, remember to keep the
distance between the fieldbus cable and the motor
cable at a minimum of 11.81 in (30 cm).
8.
The bus termination must be set for the first and last
device of the fieldbus line. See illustration below.
See also step 6 above. We recommend that the first
device on the bus terminated is the Master device.