111
CANopen external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Control word
The control word is used to control the drive operation according to the Internal State Machine.
This is mapped into the first 2 bytes of rxPDO1.
Table 144. 0x6040 control word
Bit
Name
Description
0
Switch ON
Enables drive start command
1
Disable Voltage
Enable/Disable DG1 Motor output voltage
2
Quick Stop
Stops drive with a 0.1 sec ramp when value is changed to 0.
3
Enable Operation
Enable drive start
4
Operation Mode Specific
Not Used
5
Operation Mode Specific
Not Used
6
Operation Mode Specific
Not Used
7
Reset Fault
Rising Edge resets active faults.
8
Reserved
Not Used
9
Reserved
Not Used
10
Reserved
Not Used
11
Manufacturer Specific
Not Used
12
Manufacturer Specific
Not Used
13
Manufacturer Specific
Not Used
14
Manufacturer Specific
Not Used
15
Manufacturer Specific
Not Used