119
CANopen external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Process data application mapping
Table 151. Process data application mapping
Index
Hex
Dec
Sub-Index
Name
Type
Attr.
2000
8192
Any parameter read ID
Unsigned16
RW
2001
8193
Any parameter read value
Unsigned32
RO
2002
8194
Any parameter write
Unsigned32
RW
2003
8196
Current percentage
Unsigned16
RO
2004
8195
Torque percentage
Unsigned16
RO
2005
8197
Motor nom current
Unsigned16
RW
2006
8198
Motor nom speed
Unsigned16
RW
2007
8199
Motor PF
Unsigned16
RW
2008
8200
Motor nom voltage
Unsigned16
RW
2009
8201
Motor nom frequency
Unsigned16
RW
200A
8202
Power up local remote select
Unsigned8
RW
200B
8203
Remote 1 control place
Unsigned8
RW
200C
8204
Local control place
Unsigned8
RW
200D
8205
Local reference
Unsigned8
RW
200E
8206
Remote 1 ref
Unsigned8
RW
200F
8207
Reverse enable
Unsigned8
RW
2010
8208
Fixed control word
Unsigned16
RW
2011
8209
Speed reference in percentage
Unsigned16
RW
2012
8210
FB process data in 1
Integer16
RW
2013
8211
FB process data in 2
Integer16
RW
2014
8212
FB process data in 3
Integer16
RW
2015
8213
FB process data in 4
Integer16
RW
2016
8214
FB process data in 5
Integer16
RW
2017
8215
FB process data in 6
Integer16
RW
2018
8216
Fixed status word
Unsigned16
RO
2019
8217
Actual speed in percentage
Unsigned16
RO
201A
8218
FB process data out 1
Integer16
RO
201B
8219
FB process data out 2
Integer16
RO
201C
8220
FB process data out 3
Integer16
RO
201D
8221
FB process data out 4
Integer16
RO
201E
8222
FB process data out 5
Integer16
RO
201F
8223
FB process data out 6
Integer16
RO
2063
8291
Fault code
Integer16
RO