Appendix B—Process data values
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Appendix B—Process data values
Process data OUT (slave
→
master)
The fieldbus master can read the frequency converter’s actual values using process data variables. All software applications
use process data as follows:
Table 189. Process data OUT (slave
→
master)
Data
Value
Unit
Scale
Default, Min., Max.
Process data out 1
Output frequency
Hz
0.01 Hz
Process data out 2
Motor dpeed
rpm
1 rpm
Process data out 3
Motor current
A
0.1 A
Process data out 4
Motor torque
%
0.10%
Process data out 5
Motor power
%
0.10%
Process data out 6
Motor voltage
V
0.1 V
Process data out 7
DC link voltage
V
1 V
Process data out 8
Latest fault code
otee:
N
The communication parameter group in any application has a selector parameter for every process data.
The monitoring values and drive parameters can be selected using the ID number. Default selections are shown in the
table above. Reference
Appendix A
for Modbus IDs that can be set via the keypad P20.1 FB Process Data Out group.