115
CANopen external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Fixed Status Word
Table 148. Fixed status word
Bit
Name
0
Ready
1
RUN
2
Counterclockwise
3
Faulted
4
Warning
5
Ref. Frequency reached
6
Bypass
7
Run enable
8
Not in use
9
Not in use
10
Not in use
11
Not in use
12
Not in use
13
Not in use
14
Not in use
15
Not in use
Bit
Description
Value = 0
Value = 1
0
Not Ready
Ready
1
STOP
RUN
2
Clockwise
Counterclockwise
3
—
Faulted
4
—
Warning
5
Ref. frequency not reached
Ref. Frequency reached
6
—
Motor is running in bypass
7
Disable motor run
Enable motor run
8–15
Not in use
Not in use
Actual speed percentage
The Actual Speed Percentage indicates the actual speed
value of the motor. This value will be read as a 0 to
10000 value, which indicates 0 to 100.00% speed actual.
FB process data out
The Process Data Out value is assigned by the Fieldbus
Parameter group in the application parameters. These
8 values can be set to any available Modbus ID value listed.
See
Appendix B
to reference the default Process Data Out
values assigned.