17
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
Wir
ing Set 4 0071 360 230 included
No.
Length
Number
5
350 mm
13
6
800 mm
4
7
800 mm
1
8
2000 mm
1
3.1.12 Standard-Battery Cabinet 155.6 Ah
For interconnection see chapter „Circuit Diagrams“
Standard-Battery Cabinet 155.6 Ah
The bat
tery cabinets 1
55.6
Ah
wil
l be buil
t of tw
o paral
lel con
-
nected cabinets 66.2 and 89.4 Ah
by
using
the
bat
tery
distri
-
but
ion panel (4007
1360203)
accord
ing to mount
ing circuit
diagram.
1
2
3
4
5
6
7
8
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 155.6 Ah
Rated voltage of all batteries
216 V
Number of all batteries
36 á 12 V
Battery dimensions in mm (W x H x D) 66.2 Ah
260.5 x 171 x 239
Battery dimensions in mm (W x H x D) 89.4 Ah
307.5 x 171 x 239
final pole
M-M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
1422 kg
Dimensions in mm (W x H x D)
2 x (800 x 2050 x 400)
Order no. of battery bloc 66.2 Ah
40066070902
Order no. of battery bloc 89.4 Ah
40066070821
Protection calss
IP 20
Wir
ing Set 4 0071 346 778 included
No.
Length
Number
1
440 mm
13
2
800 mm
4
3
800 mm
1
4
2000 mm
1
Wir
ing Set 4 0071 360 230 included
No.
Length
Number
5
350 mm
13
6
800 mm
4
7
800 mm
1
8
2000 mm
1
1. Battery console
1. Battery console
1. Battery console
1. Battery console
2. Battery console
2. Battery console
2. Battery console
2. Battery console
3. Battery console
3. Battery console
3. Battery console
3. Battery console
4. Battery console
4. Battery console
4. Battery console
4. Battery console
5. Battery console
5. Battery console
5. Battery console
5. Battery console