3 Technical Data / Battery Installation
3.5.7 With battery set 85.7 Ah
For interconnection see chapter „Circuit Diagrams“
*2250
ZB-S/1
0C6
ZB-S/1
8C6
ZB-S/26C6*
EURO ZB.1/264K
EURO ZB.1/264K
1
2
3
4
5
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 85.7 Ah
Rated voltage of all batteries
216 V
Number of all batteries
18 á 12 V
Battery dimensions in mm (L x W x H)
309 x 172 x 239
final pole
M-M8
Supply terminals
max. 35 mm²
W
eight incl. Batteries
685 kg
Dimensions in mm (W x H x D)
800 x 2050 x 600 (800x2250x600 for ZB-S/26C6)
Order no. batterie bloc
40066070918
Wir
ing Set 4 0071 360 231 included
No.
Length
Number
1
300 mm
12
2
360 mm
3
3
1500 mm
2
4
400 mm
1
5
1800 mm
1
3. Battery console
3. Battery console
2. Battery console
2. Battery console
1. Battery console
1. Battery console