background image

52

Mounting and Operating Instructions CEAG Battery Cabinets

   40071860035 (N)   March 2016   www.ceag.de

6 Installation

6.2.3.1 Ventilation  requirements

Ventilation of electrical rooms

Dimensions of ventilation acc. to EN 50272-2. 
The minimum air flow rate for ventilation of a battery location 

or compartment shall be calculated by the following formula:  

Q = 0.05 x n x Igas x CN x 10-3 [m

3

/h]

Q = needed air volume flow in m

3

/h 

0.05 = fixed factor
n = no. of accumulator cells
Igas = current in mA per Ah, fits 8 mA per Ah for Iboost with 

VRLA batteries
CN = capacity C10 for lead acid at 20 °C

Example for needed air volume flow of ZB-S with 155.6 Ah 

lead acid battery:
Q = 0.05 x n x Igas x CN x 10-3
Q = 0.05 x 108 x 8 x 155.6 x 10-3 m

3

/h

Q = 6.72 m

3

/h

In order to ensure the air volume flow of 6.72 m3/h, the air 

inlets and outlets in the electrical distribution room must 

have the following min. cross-sections acc. to EN 50272-2.
Vent cross-section of the air inlets and outlets:
A •  28 x Q
A •  28 x 6.72 m

3

/h

A • 188.21 cm

2

The required vents in the F90 walls must be guarded by fire 

protection measures, e.g. F90 fire shutters. 
As the calculation shows, the use of even the largest batte-

ry does not require an elaborate technical ventilation (e.g. 

explosion protected fans).
Due to the installed maintenance-free, sealed lead acid gas 

recombination batteries no further special constructional 

requirements such as a floor resistant to electrolytes or a 

floor covering (tiles) etc. have to be met.

VRLA valve regulated lead acid monobloc batteries can operate 
in any position. Except on top. 

Chart 9

Calculation of ventilation of electrical rooms acc. EN 50272-2 (calculated for boost charge!):

6.2.3.2 Close vicinity of the battery

From EN 50272-2: “…In the close vicinity of the battery the 

dilution of explosive gases is not always secured. Therefore 

a safety distance extending through air must be observed 

within which sparking or glowing devices (max. surface tem-

perature 300°C) are prohibited. The dispersion of explosive 

gas depends on the gas release rate and the ventilation close 

to the source of release. 

6.2.4 Electrical requirements (protection, insulation, 
resistance, etc.)

To prevent a build-up of static electricity when handling batte-

ries, clothing/materials, safety boots and gloves are required 

to have a surface resistance  108 Ohm and an insulation 

resistance of 105 Ohm. 
From EN 50272-2: “…To be resistant against environmental 

influences, like temperature, wetness, dust, gases, vapours 

and mechanical loads, the minimum insulation resistance 

between the battery´s circuit and other local conductive 

parts should be greater than 100 Ohm/V (of battery nominal 

voltage) corresponding to a leakage current < 10 mA.”

Note:

„Before an inspection separate the battery system from 

the fix installation and check if there is a dangerous voltage 

between the battery and its rack or cabinet. ...“   
With battery system > DC 120 V the rack or cabinet made 

of metal has to be connected to a protective conductor or 

there is a protection insulation against the battery and the 

mounting location. (Chapter 5.2 in EN 50272-2)
This insulation must withstand 4000 V for one minute. 

Note:

Protection against direct and indirect touching can be used 

for battery units with a rated voltage <= DC 120 V. In this 

case the requirements of metallic battery racks and cabinets 

are not valid (acc. to 5.2 in EN 50272-2). 
Touch protection must be provided for all active parts at 

voltages > 60 V DC with insulation, covers and distance. 

6.2.5 Installation

Batteries shall be installed in clean, dry locations. They must 

be secured against falling items and dirt. 

Battery capacity C10  
at 1.8 V/Z  and +20 °C [Ah]

5.5

8.5

14.0 23.3 32.0 39.8 50.4 53.7 66.2 85.7 89.4 106.0 118.0 143.1 155.6 178.8 195.4 245.0 268.2 308.0 357.6

Air volume flow req. for 

the ventilation of the place 

of installation [m

3

/h]

0.24 0.37 0.60 1.01 1.38 1.72 2.18 2.32 2.86 3.70 3.86 4.58 5.10 6.18 6.72 7.72 8.44 10.58 11.59 13.31 15.45

Vent cross-section  

of the air inlets and  

outlets of the place of  

installation [cm

2

]

6.6 10.3 16.9 28.2 38.7 48.1 61.0 65.0 80.1 103.7 108.1 128.2 142.7 173.1 188.2 216.3 236.4 296.3 324.4 372.6 432.5

Summary of Contents for CEAG ZB-S 10C6

Page 1: ...CEAG Battery Cabinets Mounting and Operating Instructions CEAG Battery Cabinets Target group part 1 Qualified electricans acc to DIN VDE 0105 part 1 Target group part 2 Electrical instructed persons...

Page 2: ...With battery set 357 6 Ah 23 3 2 Compact Battery Cabinets 2C3 24 3 2 1 With battery set 5 5 Ah 24 3 2 2 With battery set 8 5 Ah 25 3 2 3 With battery set 14 Ah 26 3 3 Compact Battery Cabinets 10C3 18...

Page 3: ...nity of the Battery 52 6 2 4 Electrial Requirements Protection Insulation Resistance etc 52 6 2 5 Installation 52 6 3 Preparations 53 6 4 Mounting 53 6 5 Parallel Arrangements 53 6 6 Mounting Position...

Page 4: ...Protection All information from the contents text drawings pictures and further representations are protected with regard to copy right 1 6 Spare Parts Only use original spare parts from the manufact...

Page 5: ...has approved them 2 4 Responsibility of the Operator Keep the instructions near to the battery system accessible for every person working with the battery and at all times Battery must be in a proper...

Page 6: ...3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight incl Batteries 295 kg Dimen...

Page 7: ...216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batteries 370 kg Dimensions in mm W x H x D 800 x 2050 x 4...

Page 8: ...216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 388 kg Dimensions in mm W x H x D 800 x 2050...

Page 9: ...V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 495 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 4006607...

Page 10: ...2 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 549 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 400660...

Page 11: ...V Battery dimensions in mm L x W x H 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 672 kg Dimensions in mm W x H x D 800 x 2050 x 4000 Order no batterie bloc 40066...

Page 12: ...2 V Battery dimensions in mm L x W x H 309 x 172 x 239 final pole M M8 Supply terminals max 35 mm Weight incl Batteries 685 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 400660...

Page 13: ...2 V Battery dimensions in mm L x W x H 307 5x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 750 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 4006607...

Page 14: ...x H x D 39 8 Ah 200 x 169 x 176 Battery dimensions in mm W x H x D 66 2 Ah 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 1060 kg Dimensions in mm W x H x D 2 x 800...

Page 15: ...ted voltage of all batteries 216 V Number of all batteries 36 6 V Battery dimensions in mm L x W x H 272 x 166 x 190 final pole M8 Supply terminals max 35 mm Weight incl Batteries 1200 kg Dimensions i...

Page 16: ...Battery dimensions in mm W x H x D 89 4 Ah 307 5 x 171 x 239 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 1300 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of batte...

Page 17: ...39 Battery dimensions in mm W x H x D 89 4 Ah 307 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 1422 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of bat...

Page 18: ...Rated voltage of all batteries 216 V Number of all batteries 36 12 V Battery dimensions in mm W x H x D 307 5 x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 1500 kg Dimens...

Page 19: ...minals max 35 mm Weight incl Batteries 1810 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 39 8 Ah 40066070902 Order no of bat...

Page 20: ...5 x 171 x 239 Ah Final pole M M6 Supply terminals max 35 mm Weight incl Batteries 2172 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066070902 Order no of batte...

Page 21: ...tteries 54 12 V Battery dimensions in mm L x W x H 307 5 x 171 x 239 Final pole M6 Supply terminals max 35 mm Weight incl Batteries 2250 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of...

Page 22: ...x 239 Final pole M M6 Supply terminals max 35 mm Weight incl Batteries 2638 kg Dimensions in mm W x H x D 4 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 89...

Page 23: ...ttery dimensions in mm L x W x H 307 5 x 171 x 239 Final pole M6 Supply terminals max 35 mm Weight incl Batteries 3000 kg Dimensions in mm W x H x D 4 x 800 x 2050 x 400 Order no batterie bloc 4006607...

Page 24: ...1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 5 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 65 5 x 98 Connectors S...

Page 25: ...l Data Type of battery C10 1 8 V Z 20 C 12 V 8 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 98 x 98 Connectors SR 6 3 mm Faston Su...

Page 26: ...Technical Data Type of battery C10 1 8 V Z 20 C 12 V 14 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 181 x 76 x 167 Connectors M6 Supply...

Page 27: ...1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 5 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 65 5 x 94 5 Connector...

Page 28: ...Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 98 x 94 5 Connectors 6 3 mm Faston Supply terminals max 35 mm Weight incl Batteries 170 k...

Page 29: ...C10 1 8 V Z 20 C 12 V 14 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 181 x 75 x 167 final pole M6 Supply terminals max 35 mm Weight incl...

Page 30: ...C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight in...

Page 31: ...of battery C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 m...

Page 32: ...8 V Z 20 C 12 V 32 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batte...

Page 33: ...V Z 20 C 12 V 39 8 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Ba...

Page 34: ...20 C 12 V 50 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batter...

Page 35: ...Circuit Diagrams ZB S 10C EURO ZB 1 200K EURO ZB 1 204K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 53 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batt...

Page 36: ...Type of battery C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max...

Page 37: ...8 V Z 20 C 12 V 32 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batte...

Page 38: ...S 10C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 2250 1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 39 8 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V...

Page 39: ...ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 2250 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 50 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batte...

Page 40: ...10C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 53 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batte...

Page 41: ...0C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 66 2 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batter...

Page 42: ...20 C 12 V 85 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 309 x 172 x 239 final pole M M8 Supply terminals max 35 mm Weight incl Batteri...

Page 43: ...y C10 1 8 V Z 20 C 12 V 89 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 307 5 x 171 x 239 final pole M6 Supply terminals max 35 mm Weigh...

Page 44: ...ircuit Diagrams 4 1 Wiring 5 5 Ah to 89 4 Ah 4 2 Wiring 118 Ah IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can...

Page 45: ...Distribution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sens...

Page 46: ...tribution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor c...

Page 47: ...tion Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can ca...

Page 48: ...ods Code IATA The International AirTransportation Association world wide ICAO Civil Aviation Organization sTechnical Instructions for the Safe Transport of Dangerous Goods by Air 5 6 Transport Inspect...

Page 49: ...rage period of 6 months then every 3 months afterwards storage at 30 C after a storage period of 4 months then every 2 months afterwards When measured open circuit voltage is 2 11V C battery has to be...

Page 50: ...sts of abridgements from national and international standards and guidelines See EN 50272 2 for further information Also observe Ope rating Instructions and Installation Instructions 6 2 1 Temperature...

Page 51: ...voltage 500 V 100 kOhm R 10 MOhm Note 1 To make the first part of the requirement effective personnel shall wear anti static footwear when carrying out mainte nance work on the battery The footwear sh...

Page 52: ...The dispersion of explosive gas depends on the gas release rate and the ventilation close to the source of release 6 2 4 Electrical requirements protection insulation resistance etc To prevent a build...

Page 53: ...llation work is completed lightly coat the connec tion surfaces with the terminal grease supplied This prevents corrosion but is not mandatory Check total battery voltage which should correspond to th...

Page 54: ...e and current settings the discharge conditions the temperature levels the storage conditions the cleanliness of the battery and equipment and other conditions relevant to safety issues and battery s...

Page 55: ...s can cause serious damage to the battery Ensure the same char ging state when changing the battery blocs RECOMMENDATION not more than 25 of the battery packs of a battery set should be replaced There...

Page 56: ...oned by date Security signs attached by date 1 Start Up Check all cells blocks for mechanical damage correct polarity and firmly seated connectors T orques as shown in table 1 apply for screw connecto...

Page 57: ...2 32 20 A 400 FT 2 29 2 32 20 A 500 2 30 2 35 20 A 600 2 27 2 30 20 A 700 2 27 2 30 20 T able 4 Charge voltage in buffer operation d Battery operation charge discharge operation The load is only suppl...

Page 58: ...age by more than the values given in table 7 or if the surface temperature dif ference between cells blocks exceeds 5K the service agent should be contacted Deviations of the battery voltage from the...

Page 59: ...59 Mounting and Operating Instructions CEAG Battery Cabinets 40071860035 N March 2016 www ceag de...

Page 60: ...ide a reliable efficient and safe power supply where it is needed most Eaton s experts have comprehensive in depth specialist knowledge in the area of energy management in the most diverse of sectors...

Reviews: