23
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
Wir
ing Set 4 0071 360 230 included
No.
Length
Number
1
350 mm
13
2
800 mm
4
3
800 mm
1
4
2000 mm
1
3.1.18 Standard-Battery Cabinet 357.6 Ah
Standard-Battery Cabinet 357.6 Ah
The bat
tery cabinets 357
.6
Ah
wil
l be buil
t
of f
our paral
lel con
-
nected cabinets 89.4
Ah b
y using
the bat
tery d
istribut
ion panel
(4007
1360205) accord
ing to
mount
ing circuit d
iagram.
For interconnection see chapter „Circuit Diagrams“
1
2
3
4
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 357.6 Ah
Rated voltage of all batteries
216 V
Number of all batteries
72 á 12 V
Battery dimensions in mm (L x W x H)
307.5 x 171 x 239
Final pole
M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
3000 kg
Dimensions in mm (W x H x D)
4 x (800 x 2050 x 400)
Order no. batterie bloc
40066070821
Protection calss
IP 20
4 x
Wir
ing Set 4 0071 360 230 included
No.
Length
Number
1
350 mm
13
2
800 mm
4
3
800 mm
1
4
2000 mm
1
1. Battery console
1. Battery console
1. Battery console
1. Battery console
1. Battery console
2. Battery console
2. Battery console
2. Battery console
2. Battery console
2. Battery console
3. Battery console
3. Battery console
3. Battery console
3. Battery console
3. Battery console
4. Battery console
4. Battery console
4. Battery console
4. Battery console
4. Battery console
5. Battery console
5. Battery console
5. Battery console
5. Battery console
5. Battery console