11
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
3.1.6 Standard-Battery Cabinet 66.2 Ah
For interconnection see chapter „Circuit Diagrams“
1
2
3
4
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 66.2 Ah
Rated voltage of all batteries
216 V
Number of all batteries
18 á 12 V
Battery dimensions in mm (L x W x H)
260.5 x 171 x 239
final pole
M-M6
Supply terminals
max. 35 mm²
W
eight incl. Batteries
672 kg
Dimensions in mm (W x H x D)
800 x 2050 x 4000
Order no. batterie bloc
40066070902
Protection calss
IP 20
Wir
ing Set 4 0071 346 778 included
No.
Length
Number
1
440 mm
13
2
800 mm
4
3
800 mm
1
4
2000 mm
1
Right hinge
Aperture angle 180°
Top view
Base fixing
1. Battery console
1. Battery console
2. Battery console
2. Battery console
3. Battery console
3. Battery console
4. Battery console
4. Battery console
5. Battery console
5. Battery console