53

Mounting and Operating Instructions CEAG Battery Cabinets

   40071860035 (N)   March 2016   www.ceag.de

6 Installation

6.3 Preparations

Check each cell/ monobloc separately by measuring the 

open circuit voltage.     
2 Volt cell: 

U 2.11  V

6 Volt monobloc:  U 6.33  V 
12 Volt monobloc: U 12.66  V
•   When measuring the open circuit voltage pay attention 

to polarity (perhaps wrong mounting)

•   If CEAG Notlichtsysteme GmbH has supplied drawings 

for the installations, the cells / monoblocs should be 

installed accordingly.

•   Check that the battery racks are stable and horizontal. 

For the shelf assemblies from 4 levels and  2 rows or 5 

levels and 3 rows, the assembly should be anchored with 

the building.

•   The racks or cabinets should provide adequate ventilation 

above and below to allow the heat produced by the  bat-

teries and their charging system to escape. The distance 

between cells or monoblocs shall be approx. 10  mm, at 

least 5 mm.

6.4 Mounting

For mounting use insulated tools. It is recommended to 

protect yourself by wearing rubber gloves, protection glasses 

and clothes (incl. safety boots). Remove any metal objects 

such as watches or any other items of jewelry, especially 

in the case of installation in a cabinet (see also chapter 2).
Mount the supplied terminal covers to the battery connectors 

for isolating the battery terminals.
The connections should be tightened by means of an insu-

lated torque wrench, set to the following:
•  G-M5 terminal: 5 ± 1 Nm

•  M6 male screw terminal: 6 ± 1 Nm 

•  M6 female screw terminal: 11 ± 1 Nm 

•  M8 male screw terminal: 8 ± 1 Nm 

•  M8 female screw terminal: 20 ± 1 Nm 

•  M12 male screw terminal: 25 ± 1 Nm 

•  Inch 10-32x0.425: 6 ± 1 Nm

 

After installation work is completed, lightly coat the connec-

tion surfaces with the terminal grease supplied. 
This prevents corrosion but is not mandatory.
Check total battery voltage, which should correspond to the 

number of monoblocs connected in series. The open circuit 

voltage of single cells should not vary from each other by 

more than 0.02 V among each other. For monobloc – batteries 

the following maximum differences are allowed: 
•  6 V - monobloc: 0.04 V

•  12 V - monobloc: 0.05 V

Install the provided terminal covers to insulate the battery 

poles.

6.5 Parallel Arrangements 

Preconditions and features for 2 to 10 strings in parallel:
•   The connector cables for positive and negative terminals 

of each battery string must have the same length.

•   The minimum cable size for the end connectors of a string 

is 25 mm/100 Ah string capacity.

•   The end-connector cables must be placed on a copper 

bar with at least 100 mm/100 Ah string capacity with the 

shortest possible distance.

•   It is a must to have a circuit breaker for each string or 

every two strings.

•   The strings must all have the same number of cells and 

temperature.

If these requirements are fulfilled paralleling of up to 10 

strings is possible. All battery performance data have to be 

applied to the end terminal of each string.
Also, the type of lead-acid batteries may differ as long as 

the requested charging voltage (Vpc) per string is fulfilled.
First every single string has to be pre assembled. Then check, 

if strings have the same state of charge, and therefore a si-

milar open circuit voltage, before connecting them in parallel.

6.6 Operation Positions for AGM Cells and Mono-
blocs

The following figures show the possible operation positions 

for valve regulated lead acid AGM cells and monoblocs in 

conservation-charging operation.

fig. 3: operation positions for AGM monoblocs

OK

not OK

Summary of Contents for CEAG ZB-S 10C6

Page 1: ...CEAG Battery Cabinets Mounting and Operating Instructions CEAG Battery Cabinets Target group part 1 Qualified electricans acc to DIN VDE 0105 part 1 Target group part 2 Electrical instructed persons...

Page 2: ...With battery set 357 6 Ah 23 3 2 Compact Battery Cabinets 2C3 24 3 2 1 With battery set 5 5 Ah 24 3 2 2 With battery set 8 5 Ah 25 3 2 3 With battery set 14 Ah 26 3 3 Compact Battery Cabinets 10C3 18...

Page 3: ...nity of the Battery 52 6 2 4 Electrial Requirements Protection Insulation Resistance etc 52 6 2 5 Installation 52 6 3 Preparations 53 6 4 Mounting 53 6 5 Parallel Arrangements 53 6 6 Mounting Position...

Page 4: ...Protection All information from the contents text drawings pictures and further representations are protected with regard to copy right 1 6 Spare Parts Only use original spare parts from the manufact...

Page 5: ...has approved them 2 4 Responsibility of the Operator Keep the instructions near to the battery system accessible for every person working with the battery and at all times Battery must be in a proper...

Page 6: ...3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight incl Batteries 295 kg Dimen...

Page 7: ...216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batteries 370 kg Dimensions in mm W x H x D 800 x 2050 x 4...

Page 8: ...216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 388 kg Dimensions in mm W x H x D 800 x 2050...

Page 9: ...V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 495 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 4006607...

Page 10: ...2 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 549 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 400660...

Page 11: ...V Battery dimensions in mm L x W x H 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 672 kg Dimensions in mm W x H x D 800 x 2050 x 4000 Order no batterie bloc 40066...

Page 12: ...2 V Battery dimensions in mm L x W x H 309 x 172 x 239 final pole M M8 Supply terminals max 35 mm Weight incl Batteries 685 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 400660...

Page 13: ...2 V Battery dimensions in mm L x W x H 307 5x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 750 kg Dimensions in mm W x H x D 800 x 2050 x 400 Order no batterie bloc 4006607...

Page 14: ...x H x D 39 8 Ah 200 x 169 x 176 Battery dimensions in mm W x H x D 66 2 Ah 260 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 1060 kg Dimensions in mm W x H x D 2 x 800...

Page 15: ...ted voltage of all batteries 216 V Number of all batteries 36 6 V Battery dimensions in mm L x W x H 272 x 166 x 190 final pole M8 Supply terminals max 35 mm Weight incl Batteries 1200 kg Dimensions i...

Page 16: ...Battery dimensions in mm W x H x D 89 4 Ah 307 5 x 171 x 239 final pole F M6 Supply terminals max 35 mm Weight incl Batteries 1300 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of batte...

Page 17: ...39 Battery dimensions in mm W x H x D 89 4 Ah 307 5 x 171 x 239 final pole M M6 Supply terminals max 35 mm Weight incl Batteries 1422 kg Dimensions in mm W x H x D 2 x 800 x 2050 x 400 Order no of bat...

Page 18: ...Rated voltage of all batteries 216 V Number of all batteries 36 12 V Battery dimensions in mm W x H x D 307 5 x 171 x 239 final pole M6 Supply terminals max 35 mm Weight incl Batteries 1500 kg Dimens...

Page 19: ...minals max 35 mm Weight incl Batteries 1810 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 39 8 Ah 40066070902 Order no of bat...

Page 20: ...5 x 171 x 239 Ah Final pole M M6 Supply terminals max 35 mm Weight incl Batteries 2172 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066070902 Order no of batte...

Page 21: ...tteries 54 12 V Battery dimensions in mm L x W x H 307 5 x 171 x 239 Final pole M6 Supply terminals max 35 mm Weight incl Batteries 2250 kg Dimensions in mm W x H x D 3 x 800 x 2050 x 400 Order no of...

Page 22: ...x 239 Final pole M M6 Supply terminals max 35 mm Weight incl Batteries 2638 kg Dimensions in mm W x H x D 4 x 800 x 2050 x 400 Order no of battery bloc 39 8 Ah 40066041395 Order no of battery bloc 89...

Page 23: ...ttery dimensions in mm L x W x H 307 5 x 171 x 239 Final pole M6 Supply terminals max 35 mm Weight incl Batteries 3000 kg Dimensions in mm W x H x D 4 x 800 x 2050 x 400 Order no batterie bloc 4006607...

Page 24: ...1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 5 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 65 5 x 98 Connectors S...

Page 25: ...l Data Type of battery C10 1 8 V Z 20 C 12 V 8 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 98 x 98 Connectors SR 6 3 mm Faston Su...

Page 26: ...Technical Data Type of battery C10 1 8 V Z 20 C 12 V 14 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 181 x 76 x 167 Connectors M6 Supply...

Page 27: ...1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 5 5 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 65 5 x 94 5 Connector...

Page 28: ...Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 152 x 98 x 94 5 Connectors 6 3 mm Faston Supply terminals max 35 mm Weight incl Batteries 170 k...

Page 29: ...C10 1 8 V Z 20 C 12 V 14 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 181 x 75 x 167 final pole M6 Supply terminals max 35 mm Weight incl...

Page 30: ...C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 mm Weight in...

Page 31: ...of battery C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max 35 m...

Page 32: ...8 V Z 20 C 12 V 32 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batte...

Page 33: ...V Z 20 C 12 V 39 8 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 200 x 169 x 176 final pole M M6 Supply terminals max 35 mm Weight incl Ba...

Page 34: ...20 C 12 V 50 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 220 x 172 x 235 final pole F M6 Supply terminals max 35 mm Weight incl Batter...

Page 35: ...Circuit Diagrams ZB S 10C EURO ZB 1 200K EURO ZB 1 204K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 53 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batt...

Page 36: ...Type of battery C10 1 8 V Z 20 C 12 V 23 3 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 168 x 127 x 174 final pole M6 Supply terminals max...

Page 37: ...8 V Z 20 C 12 V 32 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 198 x 168 x 175 final pole M6 Supply terminals max 35 mm Weight incl Batte...

Page 38: ...S 10C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 2250 1 2 3 4 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 39 8 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V...

Page 39: ...ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 2250 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 50 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batte...

Page 40: ...10C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 53 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batte...

Page 41: ...0C6 ZB S 18C6 ZB S 26C6 EURO ZB 1 264K EURO ZB 1 264K 1 2 3 4 5 Technical Data Type of battery C10 1 8 V Z 20 C 12 V 66 2 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Batter...

Page 42: ...20 C 12 V 85 7 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 309 x 172 x 239 final pole M M8 Supply terminals max 35 mm Weight incl Batteri...

Page 43: ...y C10 1 8 V Z 20 C 12 V 89 4 Ah Rated voltage of all batteries 216 V Number of all batteries 18 12 V Battery dimensions in mm L x W x H 307 5 x 171 x 239 final pole M6 Supply terminals max 35 mm Weigh...

Page 44: ...ircuit Diagrams 4 1 Wiring 5 5 Ah to 89 4 Ah 4 2 Wiring 118 Ah IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can...

Page 45: ...Distribution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sens...

Page 46: ...tribution Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor c...

Page 47: ...tion Panel see separate installation instruction 30080001443 IMPORTANT NOTE Only one temperature sensor per charger has to be installed A series or parallel connection of the temperature sensor can ca...

Page 48: ...ods Code IATA The International AirTransportation Association world wide ICAO Civil Aviation Organization sTechnical Instructions for the Safe Transport of Dangerous Goods by Air 5 6 Transport Inspect...

Page 49: ...rage period of 6 months then every 3 months afterwards storage at 30 C after a storage period of 4 months then every 2 months afterwards When measured open circuit voltage is 2 11V C battery has to be...

Page 50: ...sts of abridgements from national and international standards and guidelines See EN 50272 2 for further information Also observe Ope rating Instructions and Installation Instructions 6 2 1 Temperature...

Page 51: ...voltage 500 V 100 kOhm R 10 MOhm Note 1 To make the first part of the requirement effective personnel shall wear anti static footwear when carrying out mainte nance work on the battery The footwear sh...

Page 52: ...The dispersion of explosive gas depends on the gas release rate and the ventilation close to the source of release 6 2 4 Electrical requirements protection insulation resistance etc To prevent a build...

Page 53: ...llation work is completed lightly coat the connec tion surfaces with the terminal grease supplied This prevents corrosion but is not mandatory Check total battery voltage which should correspond to th...

Page 54: ...e and current settings the discharge conditions the temperature levels the storage conditions the cleanliness of the battery and equipment and other conditions relevant to safety issues and battery s...

Page 55: ...s can cause serious damage to the battery Ensure the same char ging state when changing the battery blocs RECOMMENDATION not more than 25 of the battery packs of a battery set should be replaced There...

Page 56: ...oned by date Security signs attached by date 1 Start Up Check all cells blocks for mechanical damage correct polarity and firmly seated connectors T orques as shown in table 1 apply for screw connecto...

Page 57: ...2 32 20 A 400 FT 2 29 2 32 20 A 500 2 30 2 35 20 A 600 2 27 2 30 20 A 700 2 27 2 30 20 T able 4 Charge voltage in buffer operation d Battery operation charge discharge operation The load is only suppl...

Page 58: ...age by more than the values given in table 7 or if the surface temperature dif ference between cells blocks exceeds 5K the service agent should be contacted Deviations of the battery voltage from the...

Page 59: ...59 Mounting and Operating Instructions CEAG Battery Cabinets 40071860035 N March 2016 www ceag de...

Page 60: ...ide a reliable efficient and safe power supply where it is needed most Eaton s experts have comprehensive in depth specialist knowledge in the area of energy management in the most diverse of sectors...

Reviews: