24
Mounting and Operating Instructions CEAG Battery Cabinets
40071860035 (N) March 2016 www.ceag.de
3 Technical Data / Battery Installation
3.2 Compact-Battery Cabinets 2C3
3.2.1 With battery set 5.5 Ah
For interconnection see chapter „Circuit Diagrams“
1
2
3
4
Technical D
ata
Type of battery (C10; 1.8 V/Z; +20 °C)
12 V / 5.5 Ah
Rated voltage of all batteries
216 V
Number of all batteries
18 á 12 V
Battery dimensions in mm (L x W x H)
152 x 65.5 x 98
Connectors
SR-6.3 mm (Faston)
Supply terminals
max. 35 mm²
W
eight incl. Batteries
100 kg
Dimensions in mm (W x H x D)
600 x 1000 x 300
Order no. batterie bloc
40066079643
Wir
ing Set 4 0071 346 005 included
No.
Length
Number
1
240 mm
15
2
900 mm
2
3
600 mm
1
4
1300 mm
1