DESCRIPTION:
DATE:
DRAWING NO:
INSTALLATION NOTES
SHEET:
REVISION:
G
164201118−1
11 of 19
020604
Customer Information
A−12
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
1.
In the UPS system, each battery cabinet, PDM cabinet, and transformer cabinet are crated
separately for shipping.
2.
Do not tilt cabinets more than
"
10° during handling.
3.
Dimensions are in millimeters (inches).
4.
If perforated floor tiles are required for ventilation, you should place them in front of
the UPS. Table I lists the ventilation requirements for full load operation:
Table I. Air Conditioning or Ventilation Requirements During Full Load Operation
Ratings
Input/Output Voltage
Heat Rejection*
BTU/hr
1000/hr (Kg−cal/hr)
kVA
0.8 pF
0.9 pF
Powerware 9315 400
300 kVA
400/400
71.7 (18.1)
81.0 (20.4)
400 kVA
400/400
95.6 (24.1)
107.9 (27.2)
Powerware 9315 500
400 kVA
208/208
119.0 (30.0)
133.9 (33.7)
400 kVA
480/208
107.6 (27.1)
119.7 (30.2)
400 kVA
480/480
95.6 (24.1)
107.9 (27.2)
500 kVA
480/480
119.5 (30.1)
134.9 (34.0)
500 kVA
600/600
122.9 (31.0)
138.3 (34.9)
*
Worst case scenario heat rejection data to ensure cooling capacity (includes losses from filters
and transformers).
5.
Recommended minimum clearance over the UPS module is 304.8 mm (12 in).
Required for cooling air exhaust: approximately 1420 liter/sec (3000 cfm).
6.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at 1.8 volts per cell.
7.
The battery wiring used between the battery and the UPS should not allow a voltage drop
of more than 1% of nominal DC voltage at rated battery current.
8.
A battery disconnect switch is recommended, and may be required by NEC or local codes
when batteries are remotely located. The battery disconnect switch may be supplied as an
accessory, and should be installed between battery and UPS.
9.
If the conductors used for DC input from the battery cabinet(s) to the UPS are those
provided by the UPS manufacturer, and the UPS and battery cabinet are manufactured by
the same supplier, then it is acceptable if they do not meet the noted minimum conductor
sizes.