![Eaton 9315 Installation Manual Download Page 58](http://html.mh-extra.com/html/eaton/9315/9315_installation-manual_527094058.webp)
DESCRIPTION:
DATE:
DRAWING NO:
INSTALLATION NOTES
SHEET:
REVISION:
F
164201118−1
041500
5 of 19
Customer Information
A−6
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Table E. Battery Cabinet Ratings and External Wiring Requirements
UPS
Model
Battery
Type
Cabinet
Series
Number
of
Cabinets
DC
Voltage
DC
Amps per
Cabinet
Minimum
Conductor Size
per Cabinet
(AWG or kcmil)
Number
of Wires
per
Cabinet
9315 500
500
J27
1085
4
480
300
4/0
1 pos
1 neg
500
J31
1085
4
480
300
4/0
500
J31
1085
3
480
300
350
500
J37
1085
3
480
300
350
500
J37
1085
4
480
300
4/0
500
J47
1085
3
480
300
350
500
J47
1085
4
480
300
4/0
9315 500
400
J27
1085
3
480
300
250
1 pos
1 neg
400
J27
1085
4
480
300
3/0
400
J31
1085
3
480
300
250
400
J31
1085
4
480
300
3/0
400
J37
1085
2
480
300
350
400
J37
1085
3
480
300
250
400
J37
1085
4
480
300
3/0
400
J47
1085
2
480
300
350
400
J47
1085
3
480
300
250
400
J47
1085
4
480
300
3/0
9315 400
400
J27
1085
3
420
300
4/0
1 pos
1 neg
400
J31
1085
3
420
300
300
400
J31
1085
4
420
300
4/0
400
J37
1085
3
420
300
300
400
J37
1085
4
420
300
4/0
400
J47
1085
3
420
300
300
400
J47
1085
4
420
300
4/0
9315 400
300
J27
1085
3
420
300
4/0
1 pos
1 neg
300
J27
1085
4
420
300
2/0
300
J31
1085
2
420
300
350
300
J31
1085
3
420
300
4/0
300
J31
1085
4
420
300
2/0
300
J37
1085
2
420
300
350
300
J37
1085
3
420
300
4/0
300
J37
1085
4
420
300
2/0
300
J47
1085
2
420
300
350
300
J47
1085
3
420
300
4/0
300
J47
1085
4
420
300
2/0
Summary of Contents for 9315
Page 1: ...Powerware 9315 UPS 300 500 kVA Installation Manual ...
Page 97: ......
Page 98: ... 164201118H 164201118 H ...