DESCRIPTION:
DATE:
DRAWING NO:
INSTALLATION NOTES
SHEET:
REVISION:
G
164201118−1
NOTE:
Callout letter
and
map to drawing #164201118−4
,
,
,
E
A
B
C
F
D
G
E
F
H
,
,
,
A
E
H
G
,
2 of 19
020604
Customer Information
A−3
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 500 (0.8 pF)
Ratings
Units
Rating 60 Hz
Basic unit rating at
0.8 lagging pF load
kVA
kW
400
320
400
320
500
400
500
400
INPUT/OUTPUT
VOLTAGE
208
480
480
600
AC
INPUT
AC Input to UPS Rectifier
or Input
Transformer
(0.95min. pF)
3
O
, 1 gnd, 1 Neutral (Input Transformer only)
Minimum conductor size (number per
O
)
Minimum conductor size (number per
O
)
With Filter:
Amps*
1280
560
640
512
AWG or kcmil(ea)
600(5)
500(2)
300(3)
250(3)
Without Filter:
Amps*
N/A
640
800
640
AWG or kcmil(ea)
N/A
300(3)
400(3)
300(3)
*(Maximum amps includes full load current plus bat-
tery recharge current)
AC
INPUT
AC Input to UPS Rectifier
from Input
Transformer
3
O
, 1 gnd
Minimum conductor size (number per
O
)
With Filter:
Amps
560
560
640
640
AWG or kcmil(ea)
500(2)
500(2)
300(3)
300(3)
AC
INPUT
AC Input to 5% Filter
3
O
, 1 Neutral, 1 gnd
Minimum conductor size (number per
O
)
With Filter:
Amps
N/A
560
640
N/A
AWG or kcmil(ea)
N/A
500(2)
300(3)
N/A
AC
INPUT
AC Input to UPS Rectifier
from 5%
Filter
3
O
, 1 gnd
Minimum conductor size (number per
O
)
With Filter:
Amps
N/A
560
640
N/A
AWG or kcmil(ea)
N/A
500(2)
300(3)
N/A
AC
INPUT
AC Input to UPS Bypass
or
Bypass
Transforme
r
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
1110
480
601
480
AWG or kcmil(ea)
600(5)
250(3)
300(3)
250(3)
AC
INPUT
AC Input to UPS Bypass from Bypass Trans-
former
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
560
N/A
N/A
640
AWG or kcmil(ea)
500(2)
N/A
N/A
300(3)
DC
INPUT
DC Input from Battery to UPS
(1) positive, (1) negative
Minimum conductor size (number per
O
)
VDC
Amps @ (1.8V/cell)
480
800
480
800
480
1000
480
1000
AWG or kcmil(ea)
See
Table E
See
Table E
See
Table E
See
Table E
AC
OUTPUT
AC Output to Output Transformer or Critical Load
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
480
480
601
601
AWG or kcmil(ea)
250(3)
250(3)
350(3)
350(3)
AC
OUTPUT
AC Output from Output Transformer to Critical
Load
Full Load Current
3
O
, (1) Neutral, (1) gnd
Minimum conductor size (number per
O
)
Amps
1110
N/A
N/A
480
AWG or kcmil(ea)
600(5)
N/A
N/A
4/0(3)
ISO GND
Isolated Ground Connection to Grounding
Electrode system (Optional)
Minimum conductor size (number per
O
)
AWG or kcmil(ea)
1/0 (2)