Installing a Remote Monitor Panel
9−4
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
TB1
TB2
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
ÓÓÓ
DB−9 Connector
(on UPS Communication Panel)
Figure 9-3. Wiring an RMP to the UPS
4.
Connect RMP wiring to the terminal block using terminations shown in Table 9-2.
Table 9-2. RMP Wire Terminations
From RMP A
To UPS
Remarks
TB1−4
TB3−1
Twisted wires (4)
1−2 turns per 3
″
TB1−5
TB3−2
TB1−6
TB3−3
TB1−7
TB3−4
From RMP B (if used)
To UPS
Remarks
TB1−4
TB3−5
Twisted wires (4)
1−2 turns per 3
″
TB1−5
TB3−6
TB1−6
TB3−7
TB1−7
TB3−8
5.
To check the operation of the RMP, ensure that the UPS is supplying the load via
inverter or bypass. If the indicators on the RMP show the appropriate status, then
it is operating correctly.
If the communication link between the UPS and the RMP is not present, the RMP
will self-test (all indicators flash and the horn beeps at one-second intervals). If
this occurs, check all harness connectors and the fuse for proper seating. If all
connections are secure but the RMP continues to self-test, replace the fuse with
the spare included in the hardware kit. If this does not correct the problem,
contact your service representative for verification that the RMP is working
correctly.