Installing a Remote Monitor Panel
9−3
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
Before installing an RMP, be sure you have prepared the UPS according to the instructions
in Chapter 3.
To install an RMP:
1.
Securely mount the RMP(s).
2.
Install wiring from the RMP using ½-in. conduit through the cable entry panels in
either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within the
UPS.
3.
In the spare parts kit, locate the RMP adapter cable assembly (see Figure 9-2).
Mate the DB−9 connector on the back of the terminal block into the DB−9
connector on the Communication Panel of the UPS (see Figure 9-3). Use two
screws from the spare parts kit to secure the terminal block bracket to the
Communication Panel.
Connect to
Port 1 (DB−9) on
Communication Panel
Fuse
Terminal
Block
(TB3)
Figure 9-2. Terminal Block Bracket