Installing a Relay Interface Module
10−3
EATON
Powerware
®
9315 UPS (300–500 kVA) Installation Manual
S
164201118 Rev H
www.powerware.com
4.
Connect RIM wiring to the terminal block using the terminations shown in
Table 10-1.
5.
Contact your service representative for verification and testing of the RIM and its
connections prior to making connections with J1 through J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
6.
Repeat Steps 1 through 5 for each RIM you are installing.
7.
If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter 9
or 11, respectively; otherwise, secure the UPS cabinet by reversing the steps on
page 3−4.
Table 10-1. RIM Wire Terminations
From RIM A
To UPS
Remarks
TB1−4
TB3−1
Twisted wires (4)
1−2 turns per 3
″
TB1−5
TB3−2
TB1−6
TB3−3
TB1−7
TB3−4
From RIM B (if used)
To UPS
Remarks
TB1−4
TB3−5
Twisted wires (4)
1−2 turns per 3
″
TB1−5
TB3−6
TB1−6
TB3−7
TB1−7
TB3−8