Table H. Power Cable Conduit Requirements (Cont’d)
Terminal
9315 500
9315 400
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
5% Input Filter
Output Conduit
(480/480)
(A, B, C, Gnd)
4
3 in.
3
N/A
N/A
N/A
Bypass
(A, B, C, Gnd)
5
3 in.
3
5
2.5 in.
3
Bypass Input Transformer
(Dual Feed)
Input Conduit
(A, B, C, Gnd)
5
3 in.
5
N/A
N/A
N/A
Bypass Input Transformer
(Dual Feed)
Output Conduit
(A, B, C, Gnd)
4
3 in.
2
N/A
N/A
N/A
Output
(A, B, C, Gnd)
5
3 in.
3
5
2.5 in.
3
Battery
(+), (−), Gnd
3
2.5 in.
3
3
2.5 in.
3
Summary of Contents for 9315