Section 4. Web Server Interface
4.10 Menu Items: Battery Information- Operating
This page displays active battery details including:
▪
▪
▪
▪
▪
BATT Manual Test
indicates a battery test status (
Start, Stop,
or
END
).
BATT TEST VOLT
is the configured DC output voltage for the BATT Manual Test.
TEST TIME
is the configured BATT Manual Test duration (1~1000 minutes).
TEST PERIOD
is how often the BATT Manual Test will auto-start (OFF, 1~12 months).
TEST START
(…MONTH, …DAY, …HOUR)
is a specific configured month, day, and hour to start
the BATT Manual Test; requires TEST PERIOD to be set to OFF.
▪
Batt Test Rate-
the Discharge Rate (%) as part of the BATT Manual Test Result, that determines
Battery Health.
▪
Batt Set Count-
the quantity of external -48V Battery Strings; 0,1, or 2 (BATT1 & BATT 2).
▪
EQ CHARGE TEMP-
maximum ambient temperature allowed for EQ Charge mode.
▪
CHARGE LIMIT-
maximum battery charge current per -48V Battery String.
▪
EQ CHARGE Current-
minimum charge current that will trigger FL-to-EQ transition (10~100A).
▪
EQ END Current-
maximum charge current that will trigger EQ-to-FL transition (5~50A).
▪
EQ END Time-
maximum time period that battery charge stays in EQ mode (1~20 hours).
▪
EQ PERIOD-
how often EQ mode will automatically start (10~90 days).
See
Configuration-Operate Set
page and
Configuration-Alarm Point Set
page for
additional configuration details.
Figure 13a. Battery Information- Operating page