Section 3. Installation & Cabling
(continued)
BATT CELL
3.5
Dry Relay Alarm Contacts (H/W.ALARM terminal block)
The NESPACE-KA Control Module monitors and reports the real-time status (Normal or Alarm)
in the
Status Information-Alarm
page for up to 6 Dry Relay contact alarms.
Refer to
Section 4.34 (Contact Output Used Set)
to configure each Dry Relay contact position
using the dropdown menu (choices are: Unused, Normally Closed or Normally Open. In that same
page, click the
Alarm Set
button to view alarms assigned to specific Dry Relays and to assign or
delete alarms assigned to each Dry Relay.
Physical connections are made at the 12-position
H/W.ALARM terminal block (one pair of wires per
Relay) for up to 6 Dry Relay contact alarms. The
quick-connect, spring-lock terminal block allows
for fast installation by simply pressing the solid
wire into the connector terminal until it locks. To
remove a wired connection, push the release tab
above the wired position and pull the wire out.
Figure 8a. H/W.ALARM terminal block wiring
Figure 8b. Dry Relay Alarm #1 wired connection