6
Eagle Eye Power Solutions, LLC | 877-805-3377 | www.eepowersolutions.com
Section 2. DCPS-SHELF-9KW Shelf Specifications
(continued)
2.3
Safety Requirements
2.3.1
Electro Magnetic Interference (EMI)
➢
EN61204/EN55022 Class A/
2.3.2
Surge Voltage of Power Cable
➢
Voltage
→
6kV (1.2 ×50
㎲
), Current
→
3kA (8 × 20
㎲
)
2.3.3
Leakage Current
➢
≤
30mA
2.3.4
Withstand Voltage
➢
1) between input port and output port : 1.5kVac, 1 min. or 2121Vdc, 1 min.
➢
2) between input port and chassis : 1.0kVac, 1 min. or 1414Vdc, 1 min.
2.4
Environmental Characteristics
➢
Operating Temperature & Humidity: -10
℃ ∼
+65
℃
(max); de-rates above 50
℃
➢
Operating Humidity: 0%
∼
95%, non-condensing
2.5
Mechanical Dimensions
➢
Rectifier Shelf
⇒
177mm
(H)
X 482.6mm
(W)
X 469.1mm
(D)
⇒
6.97in.
(H)
X 19.0in.
(W)
X 18.47in.
(D)
➢
Rectifier Module
⇒
122.5mm
(H)
X 85mm
(W)
X 405.5mm
(D)
⇒
4.82in.
(H)
X 3.34in.
(W)
X 15.97in.
(D)
➢
Control Module
⇒
122.5mm
(H)
X 83mm
(W)
X 405.5
(D)
⇒
4.82in.
(H)
X 3.27in.
(W)
X 15.97in.
(D)