Section 4. Web Server Interface
4.20 Menu Items: Configuration- Operate Set
(see Figure 16a)
(continued)
➢
➢
➢
➢
➢
Battery Manual Test
–
setting to enable or disable a BATT Manual Test (
Start, Stop,
or
END
).
Battery Test Volt
–
sets the DC output voltage for the BATT Manual Test.
Battery Test Time
–
sets the BATT Manual Test duration (1~1000 minutes).
Battery Test Period
–
sets how often the BATT Manual Test will auto-start (OFF, 1~12 months).
Test Start Month
- sets a specific month to start the BATT Manual Test; requires TEST PERIOD
to be set to OFF.
➢
Test Start Day
–
sets a specific day to start the BATT Manual Test; requires TEST PERIOD to be
set to OFF.
➢
Test Start Hour
–
sets a specific hour to start the BATT Manual Test; requires TEST PERIOD to
be set to OFF.
➢
Data Log Period
–
sets how often the Data Log measured data is captured (1 minute, 10
minutes, 30 minutes, or every hour)
Clicking the
button resets all Configuration-Operate Set items to factory default settings
Figure 16a. Configuration- Operate Set page