Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
48
/ 50
Setpoint
0…
23
…99
Night mode setpoint value
Fan Speed
Fan Speed 1 / Fan Speed 2 /
Fan Speed 3 /
Auto
Night mode fan speed value
Away Mode
Setpoint
0…
21
…99
Away mode setpoint value
Fan Speed
Fan Speed 1 / Fan Speed 2 / Away mode fan speed value
Fan Speed 3 /
Auto
Protect mode
Frost Protection Limit
0…
5
…99
Protect mode control mode heat
setpoint
Heat Protection Limit
0…
40
…99
Protect mode control mode cool
setpoint
Table 49
4.5.5 Communication Objects
No
Object Name
Function
Data Types
Flags
50
Regulation
On/Off
1 bit
DPT 1.002
CWT
Thermostat regulation can be turned on/off using this communication object. Also, when regulation controlled
through “Operating Mode Button” (Chapter 4.5.2) regulation status will be send using this communication
object.
56
Current Setpoint (
°C
) Temperature
2 byte
DPT 9.001
CRT
Current Setpoint (
°F
) Temperature
2 byte
DPT 9.027
CRT
Setpoint value will be send as Celsius or Fahrenheit(configured “Temperature Sensor” tab) using this
communication object, when the setpoint will be send explained in Chapter 4.5
70
Setpoint Comfort (
°C
) Temperature
2 byte
DPT 9.001
CW
Setpoint Comfort (
°F
) Temperature
2 byte
DPT 9.027
CW
Setpoint temperature for Comfort mode should be set using this communication object. Temperature value
should be compatible with selected “Temperature Unit” and setpoint limitations(Chapter 4.5.1)
71
Setpoint Night (
°C
)
Temperature
2 byte
DPT 9.001
CW
Setpoint Night (
°F
)
Temperature
2 byte
DPT 9.027
CW
Setpoint temperature for Night mode should be set using this communication object. Temperature value
should be compatible with selected “Temperature Unit” and setpoint limitations(Chapter 4.5.1)
72
Setpoint Away (
°C
)
Temperature
2 byte
DPT 9.001
CW
Setpoint Away (
°F
)
Temperature
2 byte
DPT 9.027
CW
Setpoint temperature for Away mode should be set using this communication object. Temperature value
should be compatible with selected “Temperature Unit” and setpoint limitations(Chapter 4.5.1)
73
Reset on Site
Enable
1 bit
DPT 1.003
CW
Reset on site operation should be triggered through this communication object, value to initiate operation
should be selected in “Reset on Site Value” parameter in “Setpoints” tab.
Table 50